25 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 60 m (196.9 ft).
Copper Cable (≤3% Drop)6 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.17V (2.21%)
Voltage at Load405.7 VLine Loss: 401.2 W
Max Power & Breaker17.97 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 37.07 V (8.93%) | 377.9 V | 61.14 V (14.73%) | 1605.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 22.24 V (5.36%) | 392.8 V | 36.68 V (8.84%) | 963.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 13.9 V (3.35%) | 401.1 V | 22.93 V (5.52%) | 601.9 W | ~ ≤5% |
| 6 mm² | 41 A | 32 A | 9.27 V (2.23%) | 405.7 V | 15.29 V (3.68%) | 401.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 5.56 V (1.34%) | 409.4 V | 9.17 V (2.21%) | 240.8 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 3.47 V (0.84%) | 411.5 V | 5.73 V (1.38%) | 150.5 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.22 V (0.54%) | 412.8 V | 3.67 V (0.88%) | 96.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.59 V (0.38%) | 413.4 V | 2.62 V (0.63%) | 68.8 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.11 V (0.27%) | 413.9 V | 1.83 V (0.44%) | 48.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.79 V (0.19%) | 414.2 V | 1.31 V (0.32%) | 34.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.59 V (0.14%) | 414.4 V | 0.97 V (0.23%) | 25.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.46 V (0.11%) | 414.5 V | 0.76 V (0.18%) | 20.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.37 V (0.09%) | 414.6 V | 0.61 V (0.15%) | 16.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.3 V (0.07%) | 414.7 V | 0.5 V (0.12%) | 13.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.23 V (0.06%) | 414.8 V | 0.38 V (0.09%) | 10.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.19 V (0.04%) | 414.8 V | 0.31 V (0.07%) | 8.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.14 V (0.03%) | 414.9 V | 0.23 V (0.06%) | 6.0 W | ✓ OK (≤3%) |
FAQ — 25 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 25A at 60 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 25A over 60m at 415V (voltage drop: 9.27V or 2.23%).
What is the power capacity of 25A at 415V?
At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.
Related Lengths & Currents (415V)
25A · 5m (415V)25A · 10m (415V)25A · 15m (415V)25A · 20m (415V)25A · 25m (415V)25A · 30m (415V)25A · 35m (415V)25A · 40m (415V)25A · 45m (415V)25A · 50m (415V)25A · 70m (415V)10A · 60m (415V)16A · 60m (415V)20A · 60m (415V)32A · 60m (415V)40A · 60m (415V)50A · 60m (415V)63A · 60m (415V)80A · 60m (415V)100A · 60m (415V)125A · 60m (415V)160A · 60m (415V)200A · 60m (415V)