⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.64V (1.84%)
Voltage at Load403.4 VLine Loss: 501.6 W
Max Power & Breaker17.97 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (7.44%)384.1 V50.95 V (12.28%)1337.5 WDrop High
2.5 mm²24 A18 A18.53 V (4.47%)396.5 V30.57 V (7.37%)802.5 WDrop High
4 mm²32 A25 A11.58 V (2.79%)403.4 V19.11 V (4.6%)501.6 W✓ OK (≤3%)
6 mm²41 A32 A7.72 V (1.86%)407.3 V12.74 V (3.07%)334.4 W✓ OK (≤3%)
10 mm²57 A44 A4.63 V (1.12%)410.4 V7.64 V (1.84%)200.6 W✓ OK (≤3%)
16 mm²76 A59 A2.9 V (0.7%)412.1 V4.78 V (1.15%)125.4 W✓ OK (≤3%)
25 mm²101 A78 A1.85 V (0.45%)413.1 V3.06 V (0.74%)80.2 W✓ OK (≤3%)
35 mm²125 A97 A1.32 V (0.32%)413.7 V2.18 V (0.53%)57.3 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.22%)414.1 V1.53 V (0.37%)40.1 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.16%)414.3 V1.09 V (0.26%)28.7 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.12%)414.5 V0.8 V (0.19%)21.1 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.09%)414.6 V0.64 V (0.15%)16.7 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.07%)414.7 V0.51 V (0.12%)13.4 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)414.7 V0.41 V (0.1%)10.8 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)414.8 V0.32 V (0.08%)8.4 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)414.8 V0.25 V (0.06%)6.7 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)414.9 V0.19 V (0.05%)5.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 25A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 50m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 25A at 415V?

At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.