250 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)10× 400 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.03V (45.96%)
Voltage at Load23.3 VLine Loss: 167.2 W
Max Power & Breaker6.0 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1783.33 V (7430.56%)0.0 V2941.67 V (12256.94%)445833.3 WDrop High
2.5 mm²24 A18 A1070.0 V (4458.33%)0.0 V1765.0 V (7354.17%)267500.0 WDrop High
4 mm²32 A25 A668.75 V (2786.46%)0.0 V1103.12 V (4596.35%)167187.5 WDrop High
6 mm²41 A32 A445.83 V (1857.64%)0.0 V735.42 V (3064.24%)111458.3 WDrop High
10 mm²57 A44 A267.5 V (1114.58%)0.0 V441.25 V (1838.54%)66875.0 WDrop High
16 mm²76 A59 A167.19 V (696.61%)0.0 V275.78 V (1149.09%)41796.9 WDrop High
25 mm²101 A78 A107.0 V (445.83%)0.0 V176.5 V (735.42%)26750.0 WDrop High
35 mm²125 A97 A76.43 V (318.45%)0.0 V126.07 V (525.3%)19107.1 WDrop High
50 mm²151 A118 A53.5 V (222.92%)0.0 V88.25 V (367.71%)13375.0 WDrop High
70 mm²192 A150 A38.21 V (159.23%)0.0 V63.04 V (262.65%)9553.6 WDrop High
95 mm²232 A181 A28.16 V (117.32%)0.0 V46.45 V (193.53%)7039.5 WDrop High
120 mm²269 A210 A22.29 V (92.88%)1.7 V36.77 V (153.21%)5572.9 WDrop High
150 mm²309 A241 A17.83 V (74.31%)6.2 V29.42 V (122.57%)4458.3 WDrop High
185 mm²353 A275 A14.46 V (60.25%)9.5 V23.85 V (99.38%)3614.9 WDrop High
240 mm²415 A324 A11.15 V (46.44%)12.9 V18.39 V (76.61%)2786.5 WDrop High
300 mm²477 A372 A8.92 V (37.15%)15.1 V14.71 V (61.28%)2229.2 WDrop High
400 mm²570 A445 A6.69 V (27.86%)17.3 V11.03 V (45.96%)1671.9 WDrop High

FAQ — 250 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 250A at 250 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10× 400 mm² copper cable for 250A over 250m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 250A at 24V?

At unity power factor, 250A at 24V supports 6.0 kW with a standard 250A circuit breaker.