30 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 1.2V (2.51%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.27V (2.65%)
Voltage at Load46.8 VLine Loss: 36.1 W
Max Power & Breaker1.44 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.84 V (26.75%)35.2 V21.18 V (44.12%)385.2 WDrop High
2.5 mm²24 A18 A7.7 V (16.05%)40.3 V12.71 V (26.47%)231.1 WDrop High
4 mm²32 A25 A4.82 V (10.03%)43.2 V7.94 V (16.55%)144.5 WDrop High
6 mm²41 A32 A3.21 V (6.69%)44.8 V5.29 V (11.03%)96.3 WDrop High
10 mm²57 A44 A1.93 V (4.01%)46.1 V3.18 V (6.62%)57.8 W~ ≤5%
16 mm²76 A59 A1.2 V (2.51%)46.8 V1.99 V (4.14%)36.1 W✓ OK (≤3%)
25 mm²101 A78 A0.77 V (1.61%)47.2 V1.27 V (2.65%)23.1 W✓ OK (≤3%)
35 mm²125 A97 A0.55 V (1.15%)47.4 V0.91 V (1.89%)16.5 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.8%)47.6 V0.64 V (1.32%)11.6 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.57%)47.7 V0.45 V (0.95%)8.3 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.42%)47.8 V0.33 V (0.7%)6.1 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.33%)47.8 V0.26 V (0.55%)4.8 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.27%)47.9 V0.21 V (0.44%)3.9 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.22%)47.9 V0.17 V (0.36%)3.1 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.17%)47.9 V0.13 V (0.28%)2.4 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.13%)47.9 V0.11 V (0.22%)1.9 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.1%)48.0 V0.08 V (0.17%)1.4 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 30A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 30A over 15m at 48V (voltage drop: 1.2V or 2.51%).

What is the power capacity of 30A at 48V?

At unity power factor, 30A at 48V supports 1.44 kW with a standard 30A circuit breaker.