30 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 1.28V (2.67%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 1.32V (2.76%)
Voltage at Load46.7 VLine Loss: 38.5 W
Max Power & Breaker1.44 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8.56 V (17.83%)39.4 V14.12 V (29.42%)256.8 WDrop High
2.5 mm²24 A18 A5.14 V (10.7%)42.9 V8.47 V (17.65%)154.1 WDrop High
4 mm²32 A25 A3.21 V (6.69%)44.8 V5.29 V (11.03%)96.3 WDrop High
6 mm²41 A32 A2.14 V (4.46%)45.9 V3.53 V (7.35%)64.2 W~ ≤5%
10 mm²57 A44 A1.28 V (2.67%)46.7 V2.12 V (4.41%)38.5 W✓ OK (≤3%)
16 mm²76 A59 A0.8 V (1.67%)47.2 V1.32 V (2.76%)24.1 W✓ OK (≤3%)
25 mm²101 A78 A0.51 V (1.07%)47.5 V0.85 V (1.76%)15.4 W✓ OK (≤3%)
35 mm²125 A97 A0.37 V (0.76%)47.6 V0.61 V (1.26%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.26 V (0.53%)47.7 V0.42 V (0.88%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.18 V (0.38%)47.8 V0.3 V (0.63%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.28%)47.9 V0.22 V (0.46%)4.1 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.22%)47.9 V0.18 V (0.37%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.18%)47.9 V0.14 V (0.29%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.14%)47.9 V0.11 V (0.24%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.11%)47.9 V0.09 V (0.18%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.09%)48.0 V0.07 V (0.15%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.07%)48.0 V0.05 V (0.11%)1.0 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 30A at 10 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 10m at 48V (voltage drop: 1.28V or 2.67%).

What is the power capacity of 30A at 48V?

At unity power factor, 30A at 48V supports 1.44 kW with a standard 30A circuit breaker.