30 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.03V (2.14%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 1.21V (2.52%)
Voltage at Load47.0 VLine Loss: 30.8 W
Max Power & Breaker1.44 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.12 V (35.67%)30.9 V28.24 V (58.83%)513.6 WDrop High
2.5 mm²24 A18 A10.27 V (21.4%)37.7 V16.94 V (35.3%)308.2 WDrop High
4 mm²32 A25 A6.42 V (13.38%)41.6 V10.59 V (22.06%)192.6 WDrop High
6 mm²41 A32 A4.28 V (8.92%)43.7 V7.06 V (14.71%)128.4 WDrop High
10 mm²57 A44 A2.57 V (5.35%)45.4 V4.24 V (8.82%)77.0 WDrop High
16 mm²76 A59 A1.6 V (3.34%)46.4 V2.65 V (5.52%)48.1 W~ ≤5%
25 mm²101 A78 A1.03 V (2.14%)47.0 V1.69 V (3.53%)30.8 W✓ OK (≤3%)
35 mm²125 A97 A0.73 V (1.53%)47.3 V1.21 V (2.52%)22.0 W✓ OK (≤3%)
50 mm²151 A118 A0.51 V (1.07%)47.5 V0.85 V (1.76%)15.4 W✓ OK (≤3%)
70 mm²192 A150 A0.37 V (0.76%)47.6 V0.61 V (1.26%)11.0 W✓ OK (≤3%)
95 mm²232 A181 A0.27 V (0.56%)47.7 V0.45 V (0.93%)8.1 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.45%)47.8 V0.35 V (0.74%)6.4 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.36%)47.8 V0.28 V (0.59%)5.1 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.29%)47.9 V0.23 V (0.48%)4.2 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.22%)47.9 V0.18 V (0.37%)3.2 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.18%)47.9 V0.14 V (0.29%)2.6 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.13%)47.9 V0.11 V (0.22%)1.9 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 30A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 30A over 20m at 48V (voltage drop: 1.03V or 2.14%).

What is the power capacity of 30A at 48V?

At unity power factor, 30A at 48V supports 1.44 kW with a standard 30A circuit breaker.