30 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 7.78V (1.95%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.17V (2.29%)
Voltage at Load392.2 VLine Loss: 404.5 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A129.73 V (32.43%)270.3 V213.99 V (53.5%)6741.0 WDrop High
2.5 mm²24 A18 A77.84 V (19.46%)322.2 V128.4 V (32.1%)4044.6 WDrop High
4 mm²32 A25 A48.65 V (12.16%)351.4 V80.25 V (20.06%)2527.9 WDrop High
6 mm²41 A32 A32.43 V (8.11%)367.6 V53.5 V (13.37%)1685.2 WDrop High
10 mm²57 A44 A19.46 V (4.86%)380.5 V32.1 V (8.02%)1011.1 W~ ≤5%
16 mm²76 A59 A12.16 V (3.04%)387.8 V20.06 V (5.02%)632.0 W~ ≤5%
25 mm²101 A78 A7.78 V (1.95%)392.2 V12.84 V (3.21%)404.5 W✓ OK (≤3%)
35 mm²125 A97 A5.56 V (1.39%)394.4 V9.17 V (2.29%)288.9 W✓ OK (≤3%)
50 mm²151 A118 A3.89 V (0.97%)396.1 V6.42 V (1.6%)202.2 W✓ OK (≤3%)
70 mm²192 A150 A2.78 V (0.69%)397.2 V4.59 V (1.15%)144.4 W✓ OK (≤3%)
95 mm²232 A181 A2.05 V (0.51%)398.0 V3.38 V (0.84%)106.4 W✓ OK (≤3%)
120 mm²269 A210 A1.62 V (0.41%)398.4 V2.67 V (0.67%)84.3 W✓ OK (≤3%)
150 mm²309 A241 A1.3 V (0.32%)398.7 V2.14 V (0.53%)67.4 W✓ OK (≤3%)
185 mm²353 A275 A1.05 V (0.26%)398.9 V1.74 V (0.43%)54.7 W✓ OK (≤3%)
240 mm²415 A324 A0.81 V (0.2%)399.2 V1.34 V (0.33%)42.1 W✓ OK (≤3%)
300 mm²477 A372 A0.65 V (0.16%)399.4 V1.07 V (0.27%)33.7 W✓ OK (≤3%)
400 mm²570 A445 A0.49 V (0.12%)399.5 V0.8 V (0.2%)25.3 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 30A at 175 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 30A over 175m at 400V (voltage drop: 7.78V or 1.95%).

What is the power capacity of 30A at 400V?

At unity power factor, 30A at 400V supports 20.78 kW with a standard 30A circuit breaker.