30 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 9.73V (1.41%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 10.7V (1.55%)
Voltage at Load680.3 VLine Loss: 505.6 W
Max Power & Breaker35.85 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A25.95 V (3.76%)664.1 V42.8 V (6.2%)1348.2 WDrop High
2.5 mm²24 A18 A15.57 V (2.26%)674.4 V25.68 V (3.72%)808.9 WDrop High
4 mm²32 A25 A9.73 V (1.41%)680.3 V16.05 V (2.33%)505.6 W✓ OK (≤3%)
6 mm²41 A32 A6.49 V (0.94%)683.5 V10.7 V (1.55%)337.1 W✓ OK (≤3%)
10 mm²57 A44 A3.89 V (0.56%)686.1 V6.42 V (0.93%)202.2 W✓ OK (≤3%)
16 mm²76 A59 A2.43 V (0.35%)687.6 V4.01 V (0.58%)126.4 W✓ OK (≤3%)
25 mm²101 A78 A1.56 V (0.23%)688.4 V2.57 V (0.37%)80.9 W✓ OK (≤3%)
35 mm²125 A97 A1.11 V (0.16%)688.9 V1.83 V (0.27%)57.8 W✓ OK (≤3%)
50 mm²151 A118 A0.78 V (0.11%)689.2 V1.28 V (0.19%)40.4 W✓ OK (≤3%)
70 mm²192 A150 A0.56 V (0.08%)689.4 V0.92 V (0.13%)28.9 W✓ OK (≤3%)
95 mm²232 A181 A0.41 V (0.06%)689.6 V0.68 V (0.1%)21.3 W✓ OK (≤3%)
120 mm²269 A210 A0.32 V (0.05%)689.7 V0.53 V (0.08%)16.9 W✓ OK (≤3%)
150 mm²309 A241 A0.26 V (0.04%)689.7 V0.43 V (0.06%)13.5 W✓ OK (≤3%)
185 mm²353 A275 A0.21 V (0.03%)689.8 V0.35 V (0.05%)10.9 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.02%)689.8 V0.27 V (0.04%)8.4 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.02%)689.9 V0.21 V (0.03%)6.7 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.01%)689.9 V0.16 V (0.02%)5.1 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 30A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 35m at 690V (voltage drop: 9.73V or 1.41%).

What is the power capacity of 30A at 690V?

At unity power factor, 30A at 690V supports 35.85 kW with a standard 30A circuit breaker.