30 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 6.95V (1.01%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 7.64V (1.11%)
Voltage at Load683.1 VLine Loss: 361.1 W
Max Power & Breaker35.85 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (2.69%)671.5 V30.57 V (4.43%)963.0 WDrop High
2.5 mm²24 A18 A11.12 V (1.61%)678.9 V18.34 V (2.66%)577.8 WDrop High
4 mm²32 A25 A6.95 V (1.01%)683.1 V11.46 V (1.66%)361.1 W✓ OK (≤3%)
6 mm²41 A32 A4.63 V (0.67%)685.4 V7.64 V (1.11%)240.7 W✓ OK (≤3%)
10 mm²57 A44 A2.78 V (0.4%)687.2 V4.59 V (0.66%)144.4 W✓ OK (≤3%)
16 mm²76 A59 A1.74 V (0.25%)688.3 V2.87 V (0.42%)90.3 W✓ OK (≤3%)
25 mm²101 A78 A1.11 V (0.16%)688.9 V1.83 V (0.27%)57.8 W✓ OK (≤3%)
35 mm²125 A97 A0.79 V (0.12%)689.2 V1.31 V (0.19%)41.3 W✓ OK (≤3%)
50 mm²151 A118 A0.56 V (0.08%)689.4 V0.92 V (0.13%)28.9 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.06%)689.6 V0.66 V (0.09%)20.6 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.04%)689.7 V0.48 V (0.07%)15.2 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.03%)689.8 V0.38 V (0.06%)12.0 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.03%)689.8 V0.31 V (0.04%)9.6 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.02%)689.8 V0.25 V (0.04%)7.8 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.02%)689.9 V0.19 V (0.03%)6.0 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.01%)689.9 V0.15 V (0.02%)4.8 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.01%)689.9 V0.11 V (0.02%)3.6 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 30A at 25 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 25m at 690V (voltage drop: 6.95V or 1.01%).

What is the power capacity of 30A at 690V?

At unity power factor, 30A at 690V supports 35.85 kW with a standard 30A circuit breaker.