30 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 13.9V (2.01%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 15.29V (2.22%)
Voltage at Load676.1 VLine Loss: 722.2 W
Max Power & Breaker35.85 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (5.37%)652.9 V61.14 V (8.86%)1926.0 WDrop High
2.5 mm²24 A18 A22.24 V (3.22%)667.8 V36.68 V (5.32%)1155.6 WDrop High
4 mm²32 A25 A13.9 V (2.01%)676.1 V22.93 V (3.32%)722.2 W✓ OK (≤3%)
6 mm²41 A32 A9.27 V (1.34%)680.7 V15.29 V (2.22%)481.5 W✓ OK (≤3%)
10 mm²57 A44 A5.56 V (0.81%)684.4 V9.17 V (1.33%)288.9 W✓ OK (≤3%)
16 mm²76 A59 A3.47 V (0.5%)686.5 V5.73 V (0.83%)180.6 W✓ OK (≤3%)
25 mm²101 A78 A2.22 V (0.32%)687.8 V3.67 V (0.53%)115.6 W✓ OK (≤3%)
35 mm²125 A97 A1.59 V (0.23%)688.4 V2.62 V (0.38%)82.5 W✓ OK (≤3%)
50 mm²151 A118 A1.11 V (0.16%)688.9 V1.83 V (0.27%)57.8 W✓ OK (≤3%)
70 mm²192 A150 A0.79 V (0.12%)689.2 V1.31 V (0.19%)41.3 W✓ OK (≤3%)
95 mm²232 A181 A0.59 V (0.08%)689.4 V0.97 V (0.14%)30.4 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.07%)689.5 V0.76 V (0.11%)24.1 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.05%)689.6 V0.61 V (0.09%)19.3 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.04%)689.7 V0.5 V (0.07%)15.6 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.03%)689.8 V0.38 V (0.06%)12.0 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.03%)689.8 V0.31 V (0.04%)9.6 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.02%)689.9 V0.23 V (0.03%)7.2 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 30A at 50 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 50m at 690V (voltage drop: 13.9V or 2.01%).

What is the power capacity of 30A at 690V?

At unity power factor, 30A at 690V supports 35.85 kW with a standard 30A circuit breaker.