30 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 4.17V (0.6%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.59V (0.66%)
Voltage at Load685.8 VLine Loss: 216.7 W
Max Power & Breaker35.85 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (1.61%)678.9 V18.34 V (2.66%)577.8 WDrop High
2.5 mm²24 A18 A6.67 V (0.97%)683.3 V11.01 V (1.59%)346.7 WDrop High
4 mm²32 A25 A4.17 V (0.6%)685.8 V6.88 V (1.0%)216.7 W✓ OK (≤3%)
6 mm²41 A32 A2.78 V (0.4%)687.2 V4.59 V (0.66%)144.4 W✓ OK (≤3%)
10 mm²57 A44 A1.67 V (0.24%)688.3 V2.75 V (0.4%)86.7 W✓ OK (≤3%)
16 mm²76 A59 A1.04 V (0.15%)689.0 V1.72 V (0.25%)54.2 W✓ OK (≤3%)
25 mm²101 A78 A0.67 V (0.1%)689.3 V1.1 V (0.16%)34.7 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.07%)689.5 V0.79 V (0.11%)24.8 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.05%)689.7 V0.55 V (0.08%)17.3 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.03%)689.8 V0.39 V (0.06%)12.4 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.03%)689.8 V0.29 V (0.04%)9.1 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.02%)689.9 V0.23 V (0.03%)7.2 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.02%)689.9 V0.18 V (0.03%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.01%)689.9 V0.15 V (0.02%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.01%)689.9 V0.11 V (0.02%)3.6 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)689.9 V0.09 V (0.01%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)690.0 V0.07 V (0.01%)2.2 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 30A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 15m at 690V (voltage drop: 4.17V or 0.6%).

What is the power capacity of 30A at 690V?

At unity power factor, 30A at 690V supports 35.85 kW with a standard 30A circuit breaker.