⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.53V (1.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.84V (6.21%)
Voltage at Load392.5 VLine Loss: 4238.2 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4015.47 V (1003.87%)0.0 V6623.65 V (1655.91%)2260375.0 WDrop High
2.5 mm²24 A18 A2409.28 V (602.32%)0.0 V3974.19 V (993.55%)1356225.0 WDrop High
4 mm²32 A25 A1505.8 V (376.45%)0.0 V2483.87 V (620.97%)847640.6 WDrop High
6 mm²41 A32 A1003.87 V (250.97%)0.0 V1655.91 V (413.98%)565093.8 WDrop High
10 mm²57 A44 A602.32 V (150.58%)0.0 V993.55 V (248.39%)339056.2 WDrop High
16 mm²76 A59 A376.45 V (94.11%)23.5 V620.97 V (155.24%)211910.2 WDrop High
25 mm²101 A78 A240.93 V (60.23%)159.1 V397.42 V (99.35%)135622.5 WDrop High
35 mm²125 A97 A172.09 V (43.02%)227.9 V283.87 V (70.97%)96873.2 WDrop High
50 mm²151 A118 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
70 mm²192 A150 A86.05 V (21.51%)314.0 V141.94 V (35.48%)48436.6 WDrop High
95 mm²232 A181 A63.4 V (15.85%)336.6 V104.58 V (26.15%)35690.1 WDrop High
120 mm²269 A210 A50.19 V (12.55%)349.8 V82.8 V (20.7%)28254.7 WDrop High
150 mm²309 A241 A40.15 V (10.04%)359.8 V66.24 V (16.56%)22603.8 WDrop High
185 mm²353 A275 A32.56 V (8.14%)367.4 V53.71 V (13.43%)18327.4 WDrop High
240 mm²415 A324 A25.1 V (6.27%)374.9 V41.4 V (10.35%)14127.3 WDrop High
300 mm²477 A372 A20.08 V (5.02%)379.9 V33.12 V (8.28%)11301.9 WDrop High
400 mm²570 A445 A15.06 V (3.76%)384.9 V24.84 V (6.21%)8476.4 W~ ≤5%

FAQ — 325 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 325A at 500 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 500m at 400V (voltage drop: 7.53V or 1.88%).

What is the power capacity of 325A at 400V?

At unity power factor, 325A at 400V supports 225.17 kW with a standard 350A circuit breaker.