⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

35 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.66V (2.73%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.08V (4.5%)
Voltage at Load23.3 VLine Loss: 22.9 W
Max Power & Breaker0.84 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A174.77 V (728.19%)0.0 V288.28 V (1201.18%)6116.8 WDrop High
2.5 mm²24 A18 A104.86 V (436.92%)0.0 V172.97 V (720.71%)3670.1 WDrop High
4 mm²32 A25 A65.54 V (273.07%)0.0 V108.11 V (450.44%)2293.8 WDrop High
6 mm²41 A32 A43.69 V (182.05%)0.0 V72.07 V (300.3%)1529.2 WDrop High
10 mm²57 A44 A26.21 V (109.23%)0.0 V43.24 V (180.18%)917.5 WDrop High
16 mm²76 A59 A16.38 V (68.27%)7.6 V27.03 V (112.61%)573.5 WDrop High
25 mm²101 A78 A10.49 V (43.69%)13.5 V17.3 V (72.07%)367.0 WDrop High
35 mm²125 A97 A7.49 V (31.21%)16.5 V12.35 V (51.48%)262.1 WDrop High
50 mm²151 A118 A5.24 V (21.85%)18.8 V8.65 V (36.04%)183.5 WDrop High
70 mm²192 A150 A3.74 V (15.6%)20.3 V6.18 V (25.74%)131.1 WDrop High
95 mm²232 A181 A2.76 V (11.5%)21.2 V4.55 V (18.97%)96.6 WDrop High
120 mm²269 A210 A2.18 V (9.1%)21.8 V3.6 V (15.01%)76.5 WDrop High
150 mm²309 A241 A1.75 V (7.28%)22.3 V2.88 V (12.01%)61.2 WDrop High
185 mm²353 A275 A1.42 V (5.9%)22.6 V2.34 V (9.74%)49.6 WDrop High
240 mm²415 A324 A1.09 V (4.55%)22.9 V1.8 V (7.51%)38.2 W~ ≤5%
300 mm²477 A372 A0.87 V (3.64%)23.1 V1.44 V (6.01%)30.6 W~ ≤5%
400 mm²570 A445 A0.66 V (2.73%)23.3 V1.08 V (4.5%)22.9 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 35A at 175 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 35A over 175m at 24V (voltage drop: 0.66V or 2.73%).

What is the power capacity of 35A at 24V?

At unity power factor, 35A at 24V supports 0.84 kW with a standard 35A circuit breaker.