16 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.56V (2.35%)
Voltage at Load23.3 VLine Loss: 11.0 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.98 V (66.58%)8.0 V26.36 V (109.82%)255.7 WDrop High
2.5 mm²24 A18 A9.59 V (39.95%)14.4 V15.81 V (65.89%)153.4 WDrop High
4 mm²32 A25 A5.99 V (24.97%)18.0 V9.88 V (41.18%)95.9 WDrop High
6 mm²41 A32 A3.99 V (16.64%)20.0 V6.59 V (27.46%)63.9 WDrop High
10 mm²57 A44 A2.4 V (9.99%)21.6 V3.95 V (16.47%)38.3 WDrop High
16 mm²76 A59 A1.5 V (6.24%)22.5 V2.47 V (10.3%)24.0 WDrop High
25 mm²101 A78 A0.96 V (3.99%)23.0 V1.58 V (6.59%)15.3 W~ ≤5%
35 mm²125 A97 A0.68 V (2.85%)23.3 V1.13 V (4.71%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.48 V (2.0%)23.5 V0.79 V (3.29%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.34 V (1.43%)23.7 V0.56 V (2.35%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.25 V (1.05%)23.7 V0.42 V (1.73%)4.0 W✓ OK (≤3%)
120 mm²269 A210 A0.2 V (0.83%)23.8 V0.33 V (1.37%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.16 V (0.67%)23.8 V0.26 V (1.1%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.54%)23.9 V0.21 V (0.89%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.42%)23.9 V0.16 V (0.69%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.33%)23.9 V0.13 V (0.55%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.25%)23.9 V0.1 V (0.41%)1.0 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 35 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 16A over 35m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.