25 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 0.53V (2.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.65V (2.71%)
Voltage at Load23.5 VLine Loss: 13.4 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.97 V (104.03%)0.0 V41.18 V (171.6%)624.2 WDrop High
2.5 mm²24 A18 A14.98 V (62.42%)9.0 V24.71 V (102.96%)374.5 WDrop High
4 mm²32 A25 A9.36 V (39.01%)14.6 V15.44 V (64.35%)234.1 WDrop High
6 mm²41 A32 A6.24 V (26.01%)17.8 V10.3 V (42.9%)156.0 WDrop High
10 mm²57 A44 A3.74 V (15.6%)20.3 V6.18 V (25.74%)93.6 WDrop High
16 mm²76 A59 A2.34 V (9.75%)21.7 V3.86 V (16.09%)58.5 WDrop High
25 mm²101 A78 A1.5 V (6.24%)22.5 V2.47 V (10.3%)37.5 WDrop High
35 mm²125 A97 A1.07 V (4.46%)22.9 V1.76 V (7.35%)26.8 W~ ≤5%
50 mm²151 A118 A0.75 V (3.12%)23.3 V1.24 V (5.15%)18.7 W~ ≤5%
70 mm²192 A150 A0.53 V (2.23%)23.5 V0.88 V (3.68%)13.4 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (1.64%)23.6 V0.65 V (2.71%)9.9 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (1.3%)23.7 V0.51 V (2.14%)7.8 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (1.04%)23.8 V0.41 V (1.72%)6.2 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.84%)23.8 V0.33 V (1.39%)5.1 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.65%)23.8 V0.26 V (1.07%)3.9 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.52%)23.9 V0.21 V (0.86%)3.1 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.39%)23.9 V0.15 V (0.64%)2.3 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 35 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 25A over 35m at 24V (voltage drop: 0.53V or 2.23%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.