35 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 18.16V (2.63%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 14.98V (2.17%)
Voltage at Load671.8 VLine Loss: 1101.0 W
Max Power & Breaker41.83 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A302.7 V (43.87%)387.3 V499.32 V (72.37%)18350.5 WDrop High
2.5 mm²24 A18 A181.62 V (26.32%)508.4 V299.59 V (43.42%)11010.3 WDrop High
4 mm²32 A25 A113.51 V (16.45%)576.5 V187.25 V (27.14%)6881.4 WDrop High
6 mm²41 A32 A75.68 V (10.97%)614.3 V124.83 V (18.09%)4587.6 WDrop High
10 mm²57 A44 A45.41 V (6.58%)644.6 V74.9 V (10.85%)2752.6 WDrop High
16 mm²76 A59 A28.38 V (4.11%)661.6 V46.81 V (6.78%)1720.4 W~ ≤5%
25 mm²101 A78 A18.16 V (2.63%)671.8 V29.96 V (4.34%)1101.0 W✓ OK (≤3%)
35 mm²125 A97 A12.97 V (1.88%)677.0 V21.4 V (3.1%)786.4 W✓ OK (≤3%)
50 mm²151 A118 A9.08 V (1.32%)680.9 V14.98 V (2.17%)550.5 W✓ OK (≤3%)
70 mm²192 A150 A6.49 V (0.94%)683.5 V10.7 V (1.55%)393.2 W✓ OK (≤3%)
95 mm²232 A181 A4.78 V (0.69%)685.2 V7.88 V (1.14%)289.7 W✓ OK (≤3%)
120 mm²269 A210 A3.78 V (0.55%)686.2 V6.24 V (0.9%)229.4 W✓ OK (≤3%)
150 mm²309 A241 A3.03 V (0.44%)687.0 V4.99 V (0.72%)183.5 W✓ OK (≤3%)
185 mm²353 A275 A2.45 V (0.36%)687.5 V4.05 V (0.59%)148.8 W✓ OK (≤3%)
240 mm²415 A324 A1.89 V (0.27%)688.1 V3.12 V (0.45%)114.7 W✓ OK (≤3%)
300 mm²477 A372 A1.51 V (0.22%)688.5 V2.5 V (0.36%)91.8 W✓ OK (≤3%)
400 mm²570 A445 A1.14 V (0.16%)688.9 V1.87 V (0.27%)68.8 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 35A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 35A over 350m at 690V (voltage drop: 18.16V or 2.63%).

What is the power capacity of 35A at 690V?

At unity power factor, 35A at 690V supports 41.83 kW with a standard 35A circuit breaker.