32 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 50 m (164.0 ft).
Copper Cable (≤3% Drop)4 mm²Drop: 14.83V (2.15%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 16.3V (2.36%)
Voltage at Load675.2 VLine Loss: 821.8 W
Max Power & Breaker38.24 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 39.54 V (5.73%) | 650.5 V | 65.22 V (9.45%) | 2191.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 23.72 V (3.44%) | 666.3 V | 39.13 V (5.67%) | 1314.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 14.83 V (2.15%) | 675.2 V | 24.46 V (3.54%) | 821.8 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 9.88 V (1.43%) | 680.1 V | 16.3 V (2.36%) | 547.8 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 5.93 V (0.86%) | 684.1 V | 9.78 V (1.42%) | 328.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 3.71 V (0.54%) | 686.3 V | 6.11 V (0.89%) | 205.4 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.37 V (0.34%) | 687.6 V | 3.91 V (0.57%) | 131.5 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.69 V (0.25%) | 688.3 V | 2.8 V (0.41%) | 93.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.19 V (0.17%) | 688.8 V | 1.96 V (0.28%) | 65.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.85 V (0.12%) | 689.2 V | 1.4 V (0.2%) | 47.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.62 V (0.09%) | 689.4 V | 1.03 V (0.15%) | 34.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.49 V (0.07%) | 689.5 V | 0.82 V (0.12%) | 27.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.4 V (0.06%) | 689.6 V | 0.65 V (0.09%) | 21.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.32 V (0.05%) | 689.7 V | 0.53 V (0.08%) | 17.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.25 V (0.04%) | 689.8 V | 0.41 V (0.06%) | 13.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.2 V (0.03%) | 689.8 V | 0.33 V (0.05%) | 11.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.15 V (0.02%) | 689.9 V | 0.24 V (0.04%) | 8.2 W | ✓ OK (≤3%) |
FAQ — 32 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 32A at 50 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 50m at 690V (voltage drop: 14.83V or 2.15%).
What is the power capacity of 32A at 690V?
At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.
Related Lengths & Currents (690V)
32A · 5m (690V)32A · 10m (690V)32A · 15m (690V)32A · 20m (690V)32A · 25m (690V)32A · 30m (690V)32A · 35m (690V)32A · 40m (690V)32A · 45m (690V)32A · 60m (690V)32A · 70m (690V)10A · 50m (690V)16A · 50m (690V)20A · 50m (690V)25A · 50m (690V)40A · 50m (690V)50A · 50m (690V)63A · 50m (690V)80A · 50m (690V)100A · 50m (690V)125A · 50m (690V)160A · 50m (690V)200A · 50m (690V)