350 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.05V (0.25%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.07V (0.26%)
Voltage at Load413.9 VLine Loss: 637.7 W
Max Power & Breaker251.58 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A129.73 V (31.26%)285.3 V213.99 V (51.57%)78645.0 WDrop High
2.5 mm²24 A18 A77.84 V (18.76%)337.2 V128.4 V (30.94%)47187.0 WDrop High
4 mm²32 A25 A48.65 V (11.72%)366.4 V80.25 V (19.34%)29491.9 WDrop High
6 mm²41 A32 A32.43 V (7.82%)382.6 V53.5 V (12.89%)19661.2 WDrop High
10 mm²57 A44 A19.46 V (4.69%)395.5 V32.1 V (7.73%)11796.8 WDrop High
16 mm²76 A59 A12.16 V (2.93%)402.8 V20.06 V (4.83%)7373.0 WDrop High
25 mm²101 A78 A7.78 V (1.88%)407.2 V12.84 V (3.09%)4718.7 WDrop High
35 mm²125 A97 A5.56 V (1.34%)409.4 V9.17 V (2.21%)3370.5 WDrop High
50 mm²151 A118 A3.89 V (0.94%)411.1 V6.42 V (1.55%)2359.3 WDrop High
70 mm²192 A150 A2.78 V (0.67%)412.2 V4.59 V (1.1%)1685.2 WDrop High
95 mm²232 A181 A2.05 V (0.49%)413.0 V3.38 V (0.81%)1241.8 WDrop High
120 mm²269 A210 A1.62 V (0.39%)413.4 V2.67 V (0.64%)983.1 WDrop High
150 mm²309 A241 A1.3 V (0.31%)413.7 V2.14 V (0.52%)786.5 WDrop High
185 mm²353 A275 A1.05 V (0.25%)413.9 V1.74 V (0.42%)637.7 W✓ OK (≤3%)
240 mm²415 A324 A0.81 V (0.2%)414.2 V1.34 V (0.32%)491.5 W✓ OK (≤3%)
300 mm²477 A372 A0.65 V (0.16%)414.4 V1.07 V (0.26%)393.2 W✓ OK (≤3%)
400 mm²570 A445 A0.49 V (0.12%)414.5 V0.8 V (0.19%)294.9 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 350A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 15m at 415V (voltage drop: 1.05V or 0.25%).

What is the power capacity of 350A at 415V?

At unity power factor, 350A at 415V supports 251.58 kW with a standard 350A circuit breaker.