⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

350 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.4V (0.34%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.43V (0.34%)
Voltage at Load413.6 VLine Loss: 850.2 W
Max Power & Breaker251.58 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A172.97 V (41.68%)242.0 V285.33 V (68.75%)104860.0 WDrop High
2.5 mm²24 A18 A103.78 V (25.01%)311.2 V171.2 V (41.25%)62916.0 WDrop High
4 mm²32 A25 A64.87 V (15.63%)350.1 V107.0 V (25.78%)39322.5 WDrop High
6 mm²41 A32 A43.24 V (10.42%)371.8 V71.33 V (17.19%)26215.0 WDrop High
10 mm²57 A44 A25.95 V (6.25%)389.1 V42.8 V (10.31%)15729.0 WDrop High
16 mm²76 A59 A16.22 V (3.91%)398.8 V26.75 V (6.45%)9830.6 WDrop High
25 mm²101 A78 A10.38 V (2.5%)404.6 V17.12 V (4.13%)6291.6 WDrop High
35 mm²125 A97 A7.41 V (1.79%)407.6 V12.23 V (2.95%)4494.0 WDrop High
50 mm²151 A118 A5.19 V (1.25%)409.8 V8.56 V (2.06%)3145.8 WDrop High
70 mm²192 A150 A3.71 V (0.89%)411.3 V6.11 V (1.47%)2247.0 WDrop High
95 mm²232 A181 A2.73 V (0.66%)412.3 V4.51 V (1.09%)1655.7 WDrop High
120 mm²269 A210 A2.16 V (0.52%)412.8 V3.57 V (0.86%)1310.8 WDrop High
150 mm²309 A241 A1.73 V (0.42%)413.3 V2.85 V (0.69%)1048.6 WDrop High
185 mm²353 A275 A1.4 V (0.34%)413.6 V2.31 V (0.56%)850.2 W✓ OK (≤3%)
240 mm²415 A324 A1.08 V (0.26%)413.9 V1.78 V (0.43%)655.4 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (0.21%)414.1 V1.43 V (0.34%)524.3 W✓ OK (≤3%)
400 mm²570 A445 A0.65 V (0.16%)414.4 V1.07 V (0.26%)393.2 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 350A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 20m at 415V (voltage drop: 1.4V or 0.34%).

What is the power capacity of 350A at 415V?

At unity power factor, 350A at 415V supports 251.58 kW with a standard 350A circuit breaker.