⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

350 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.21V (2.53%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.24V (2.57%)
Voltage at Load46.8 VLine Loss: 425.1 W
Max Power & Breaker16.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A149.8 V (312.08%)0.0 V247.1 V (514.79%)52430.0 WDrop High
2.5 mm²24 A18 A89.88 V (187.25%)0.0 V148.26 V (308.87%)31458.0 WDrop High
4 mm²32 A25 A56.18 V (117.03%)0.0 V92.66 V (193.05%)19661.2 WDrop High
6 mm²41 A32 A37.45 V (78.02%)10.6 V61.77 V (128.7%)13107.5 WDrop High
10 mm²57 A44 A22.47 V (46.81%)25.5 V37.06 V (77.22%)7864.5 WDrop High
16 mm²76 A59 A14.04 V (29.26%)34.0 V23.17 V (48.26%)4915.3 WDrop High
25 mm²101 A78 A8.99 V (18.73%)39.0 V14.83 V (30.89%)3145.8 WDrop High
35 mm²125 A97 A6.42 V (13.38%)41.6 V10.59 V (22.06%)2247.0 WDrop High
50 mm²151 A118 A4.49 V (9.36%)43.5 V7.41 V (15.44%)1572.9 WDrop High
70 mm²192 A150 A3.21 V (6.69%)44.8 V5.29 V (11.03%)1123.5 WDrop High
95 mm²232 A181 A2.37 V (4.93%)45.6 V3.9 V (8.13%)827.8 WDrop High
120 mm²269 A210 A1.87 V (3.9%)46.1 V3.09 V (6.43%)655.4 WDrop High
150 mm²309 A241 A1.5 V (3.12%)46.5 V2.47 V (5.15%)524.3 WDrop High
185 mm²353 A275 A1.21 V (2.53%)46.8 V2.0 V (4.17%)425.1 W✓ OK (≤3%)
240 mm²415 A324 A0.94 V (1.95%)47.1 V1.54 V (3.22%)327.7 W✓ OK (≤3%)
300 mm²477 A372 A0.75 V (1.56%)47.3 V1.24 V (2.57%)262.1 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (1.17%)47.4 V0.93 V (1.93%)196.6 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 350A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 15m at 48V (voltage drop: 1.21V or 2.53%).

What is the power capacity of 350A at 48V?

At unity power factor, 350A at 48V supports 16.8 kW with a standard 350A circuit breaker.