350 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.94V (1.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.09V (6.43%)
Voltage at Load47.1 VLine Loss: 327.7 W
Max Power & Breaker16.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A499.33 V (1040.28%)0.0 V823.67 V (1715.97%)174766.7 WDrop High
2.5 mm²24 A18 A299.6 V (624.17%)0.0 V494.2 V (1029.58%)104860.0 WDrop High
4 mm²32 A25 A187.25 V (390.1%)0.0 V308.88 V (643.49%)65537.5 WDrop High
6 mm²41 A32 A124.83 V (260.07%)0.0 V205.92 V (428.99%)43691.7 WDrop High
10 mm²57 A44 A74.9 V (156.04%)0.0 V123.55 V (257.4%)26215.0 WDrop High
16 mm²76 A59 A46.81 V (97.53%)1.2 V77.22 V (160.87%)16384.4 WDrop High
25 mm²101 A78 A29.96 V (62.42%)18.0 V49.42 V (102.96%)10486.0 WDrop High
35 mm²125 A97 A21.4 V (44.58%)26.6 V35.3 V (73.54%)7490.0 WDrop High
50 mm²151 A118 A14.98 V (31.21%)33.0 V24.71 V (51.48%)5243.0 WDrop High
70 mm²192 A150 A10.7 V (22.29%)37.3 V17.65 V (36.77%)3745.0 WDrop High
95 mm²232 A181 A7.88 V (16.43%)40.1 V13.01 V (27.09%)2759.5 WDrop High
120 mm²269 A210 A6.24 V (13.0%)41.8 V10.3 V (21.45%)2184.6 WDrop High
150 mm²309 A241 A4.99 V (10.4%)43.0 V8.24 V (17.16%)1747.7 WDrop High
185 mm²353 A275 A4.05 V (8.43%)44.0 V6.68 V (13.91%)1417.0 WDrop High
240 mm²415 A324 A3.12 V (6.5%)44.9 V5.15 V (10.72%)1092.3 WDrop High
300 mm²477 A372 A2.5 V (5.2%)45.5 V4.12 V (8.58%)873.8 WDrop High
400 mm²570 A445 A1.87 V (3.9%)46.1 V3.09 V (6.43%)655.4 W~ ≤5%

FAQ — 350 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 350A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 350A over 50m at 48V (voltage drop: 0.94V or 1.95%).

What is the power capacity of 350A at 48V?

At unity power factor, 350A at 48V supports 16.8 kW with a standard 350A circuit breaker.