350 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.4V (0.84%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.41V (0.86%)
Voltage at Load47.6 VLine Loss: 141.7 W
Max Power & Breaker16.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.93 V (104.03%)0.0 V82.37 V (171.6%)17476.7 WDrop High
2.5 mm²24 A18 A29.96 V (62.42%)18.0 V49.42 V (102.96%)10486.0 WDrop High
4 mm²32 A25 A18.72 V (39.01%)29.3 V30.89 V (64.35%)6553.8 WDrop High
6 mm²41 A32 A12.48 V (26.01%)35.5 V20.59 V (42.9%)4369.2 WDrop High
10 mm²57 A44 A7.49 V (15.6%)40.5 V12.35 V (25.74%)2621.5 WDrop High
16 mm²76 A59 A4.68 V (9.75%)43.3 V7.72 V (16.09%)1638.4 WDrop High
25 mm²101 A78 A3.0 V (6.24%)45.0 V4.94 V (10.3%)1048.6 WDrop High
35 mm²125 A97 A2.14 V (4.46%)45.9 V3.53 V (7.35%)749.0 WDrop High
50 mm²151 A118 A1.5 V (3.12%)46.5 V2.47 V (5.15%)524.3 WDrop High
70 mm²192 A150 A1.07 V (2.23%)46.9 V1.76 V (3.68%)374.5 WDrop High
95 mm²232 A181 A0.79 V (1.64%)47.2 V1.3 V (2.71%)275.9 WDrop High
120 mm²269 A210 A0.62 V (1.3%)47.4 V1.03 V (2.14%)218.5 WDrop High
150 mm²309 A241 A0.5 V (1.04%)47.5 V0.82 V (1.72%)174.8 WDrop High
185 mm²353 A275 A0.4 V (0.84%)47.6 V0.67 V (1.39%)141.7 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.65%)47.7 V0.51 V (1.07%)109.2 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.52%)47.8 V0.41 V (0.86%)87.4 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.39%)47.8 V0.31 V (0.64%)65.5 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 350A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 5m at 48V (voltage drop: 0.4V or 0.84%).

What is the power capacity of 350A at 48V?

At unity power factor, 350A at 48V supports 16.8 kW with a standard 350A circuit breaker.