375 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 6.95V (1.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (1.66%)
Voltage at Load408.1 VLine Loss: 4514.1 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)722250.0 WDrop High
2.5 mm²24 A18 A667.19 V (160.77%)0.0 V1100.55 V (265.19%)433350.0 WDrop High
4 mm²32 A25 A416.99 V (100.48%)0.0 V687.84 V (165.74%)270843.8 WDrop High
6 mm²41 A32 A277.99 V (66.99%)137.0 V458.56 V (110.5%)180562.5 WDrop High
10 mm²57 A44 A166.8 V (40.19%)248.2 V275.14 V (66.3%)108337.5 WDrop High
16 mm²76 A59 A104.25 V (25.12%)310.8 V171.96 V (41.44%)67710.9 WDrop High
25 mm²101 A78 A66.72 V (16.08%)348.3 V110.05 V (26.52%)43335.0 WDrop High
35 mm²125 A97 A47.66 V (11.48%)367.3 V78.61 V (18.94%)30953.6 WDrop High
50 mm²151 A118 A33.36 V (8.04%)381.6 V55.03 V (13.26%)21667.5 WDrop High
70 mm²192 A150 A23.83 V (5.74%)391.2 V39.31 V (9.47%)15476.8 WDrop High
95 mm²232 A181 A17.56 V (4.23%)397.4 V28.96 V (6.98%)11403.9 WDrop High
120 mm²269 A210 A13.9 V (3.35%)401.1 V22.93 V (5.52%)9028.1 WDrop High
150 mm²309 A241 A11.12 V (2.68%)403.9 V18.34 V (4.42%)7222.5 WDrop High
185 mm²353 A275 A9.02 V (2.17%)406.0 V14.87 V (3.58%)5856.1 WDrop High
240 mm²415 A324 A6.95 V (1.67%)408.1 V11.46 V (2.76%)4514.1 W✓ OK (≤3%)
300 mm²477 A372 A5.56 V (1.34%)409.4 V9.17 V (2.21%)3611.2 W✓ OK (≤3%)
400 mm²570 A445 A4.17 V (1.0%)410.8 V6.88 V (1.66%)2708.4 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 120m at 415V (voltage drop: 6.95V or 1.67%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.