⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 8.69V (1.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.6V (1.25%)
Voltage at Load681.3 VLine Loss: 5642.6 W
Max Power & Breaker448.17 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1389.97 V (201.45%)0.0 V2292.8 V (332.29%)902812.5 WDrop High
2.5 mm²24 A18 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)541687.5 WDrop High
4 mm²32 A25 A521.24 V (75.54%)168.8 V859.8 V (124.61%)338554.7 WDrop High
6 mm²41 A32 A347.49 V (50.36%)342.5 V573.2 V (83.07%)225703.1 WDrop High
10 mm²57 A44 A208.5 V (30.22%)481.5 V343.92 V (49.84%)135421.9 WDrop High
16 mm²76 A59 A130.31 V (18.89%)559.7 V214.95 V (31.15%)84638.7 WDrop High
25 mm²101 A78 A83.4 V (12.09%)606.6 V137.57 V (19.94%)54168.7 WDrop High
35 mm²125 A97 A59.57 V (8.63%)630.4 V98.26 V (14.24%)38692.0 WDrop High
50 mm²151 A118 A41.7 V (6.04%)648.3 V68.78 V (9.97%)27084.4 WDrop High
70 mm²192 A150 A29.79 V (4.32%)660.2 V49.13 V (7.12%)19346.0 WDrop High
95 mm²232 A181 A21.95 V (3.18%)668.1 V36.2 V (5.25%)14254.9 WDrop High
120 mm²269 A210 A17.37 V (2.52%)672.6 V28.66 V (4.15%)11285.2 WDrop High
150 mm²309 A241 A13.9 V (2.01%)676.1 V22.93 V (3.32%)9028.1 WDrop High
185 mm²353 A275 A11.27 V (1.63%)678.7 V18.59 V (2.69%)7320.1 WDrop High
240 mm²415 A324 A8.69 V (1.26%)681.3 V14.33 V (2.08%)5642.6 W✓ OK (≤3%)
300 mm²477 A372 A6.95 V (1.01%)683.1 V11.46 V (1.66%)4514.1 W✓ OK (≤3%)
400 mm²570 A445 A5.21 V (0.76%)684.8 V8.6 V (1.25%)3385.5 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 375A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 150m at 690V (voltage drop: 8.69V or 1.26%).

What is the power capacity of 375A at 690V?

At unity power factor, 375A at 690V supports 448.17 kW with a standard 400A circuit breaker.