375 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.32V (2.76%)
Voltage at Load46.7 VLine Loss: 501.6 W
Max Power & Breaker18.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A214.0 V (445.83%)0.0 V353.0 V (735.42%)80250.0 WDrop High
2.5 mm²24 A18 A128.4 V (267.5%)0.0 V211.8 V (441.25%)48150.0 WDrop High
4 mm²32 A25 A80.25 V (167.19%)0.0 V132.38 V (275.78%)30093.8 WDrop High
6 mm²41 A32 A53.5 V (111.46%)0.0 V88.25 V (183.85%)20062.5 WDrop High
10 mm²57 A44 A32.1 V (66.88%)15.9 V52.95 V (110.31%)12037.5 WDrop High
16 mm²76 A59 A20.06 V (41.8%)27.9 V33.09 V (68.95%)7523.4 WDrop High
25 mm²101 A78 A12.84 V (26.75%)35.2 V21.18 V (44.12%)4815.0 WDrop High
35 mm²125 A97 A9.17 V (19.11%)38.8 V15.13 V (31.52%)3439.3 WDrop High
50 mm²151 A118 A6.42 V (13.38%)41.6 V10.59 V (22.06%)2407.5 WDrop High
70 mm²192 A150 A4.59 V (9.55%)43.4 V7.56 V (15.76%)1719.6 WDrop High
95 mm²232 A181 A3.38 V (7.04%)44.6 V5.57 V (11.61%)1267.1 WDrop High
120 mm²269 A210 A2.68 V (5.57%)45.3 V4.41 V (9.19%)1003.1 WDrop High
150 mm²309 A241 A2.14 V (4.46%)45.9 V3.53 V (7.35%)802.5 WDrop High
185 mm²353 A275 A1.74 V (3.61%)46.3 V2.86 V (5.96%)650.7 WDrop High
240 mm²415 A324 A1.34 V (2.79%)46.7 V2.21 V (4.6%)501.6 W✓ OK (≤3%)
300 mm²477 A372 A1.07 V (2.23%)46.9 V1.76 V (3.68%)401.2 W✓ OK (≤3%)
400 mm²570 A445 A0.8 V (1.67%)47.2 V1.32 V (2.76%)300.9 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 375A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 20m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 375A at 48V?

At unity power factor, 375A at 48V supports 18.0 kW with a standard 400A circuit breaker.