⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.67V (1.39%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.66V (1.38%)
Voltage at Load47.3 VLine Loss: 250.8 W
Max Power & Breaker18.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A107.0 V (222.92%)0.0 V176.5 V (367.71%)40125.0 WDrop High
2.5 mm²24 A18 A64.2 V (133.75%)0.0 V105.9 V (220.62%)24075.0 WDrop High
4 mm²32 A25 A40.12 V (83.59%)7.9 V66.19 V (137.89%)15046.9 WDrop High
6 mm²41 A32 A26.75 V (55.73%)21.2 V44.12 V (91.93%)10031.2 WDrop High
10 mm²57 A44 A16.05 V (33.44%)31.9 V26.47 V (55.16%)6018.8 WDrop High
16 mm²76 A59 A10.03 V (20.9%)38.0 V16.55 V (34.47%)3761.7 WDrop High
25 mm²101 A78 A6.42 V (13.38%)41.6 V10.59 V (22.06%)2407.5 WDrop High
35 mm²125 A97 A4.59 V (9.55%)43.4 V7.56 V (15.76%)1719.6 WDrop High
50 mm²151 A118 A3.21 V (6.69%)44.8 V5.29 V (11.03%)1203.8 WDrop High
70 mm²192 A150 A2.29 V (4.78%)45.7 V3.78 V (7.88%)859.8 WDrop High
95 mm²232 A181 A1.69 V (3.52%)46.3 V2.79 V (5.81%)633.6 WDrop High
120 mm²269 A210 A1.34 V (2.79%)46.7 V2.21 V (4.6%)501.6 WDrop High
150 mm²309 A241 A1.07 V (2.23%)46.9 V1.76 V (3.68%)401.2 WDrop High
185 mm²353 A275 A0.87 V (1.81%)47.1 V1.43 V (2.98%)325.3 WDrop High
240 mm²415 A324 A0.67 V (1.39%)47.3 V1.1 V (2.3%)250.8 W✓ OK (≤3%)
300 mm²477 A372 A0.53 V (1.11%)47.5 V0.88 V (1.84%)200.6 W✓ OK (≤3%)
400 mm²570 A445 A0.4 V (0.84%)47.6 V0.66 V (1.38%)150.5 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 375A at 10 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 10m at 48V (voltage drop: 0.67V or 1.39%).

What is the power capacity of 375A at 48V?

At unity power factor, 375A at 48V supports 18.0 kW with a standard 400A circuit breaker.