⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.65V (3.45%)
Voltage at Load46.7 VLine Loss: 501.6 W
Max Power & Breaker18.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A267.5 V (557.29%)0.0 V441.25 V (919.27%)100312.5 WDrop High
2.5 mm²24 A18 A160.5 V (334.37%)0.0 V264.75 V (551.56%)60187.5 WDrop High
4 mm²32 A25 A100.31 V (208.98%)0.0 V165.47 V (344.73%)37617.2 WDrop High
6 mm²41 A32 A66.88 V (139.32%)0.0 V110.31 V (229.82%)25078.1 WDrop High
10 mm²57 A44 A40.12 V (83.59%)7.9 V66.19 V (137.89%)15046.9 WDrop High
16 mm²76 A59 A25.08 V (52.25%)22.9 V41.37 V (86.18%)9404.3 WDrop High
25 mm²101 A78 A16.05 V (33.44%)32.0 V26.47 V (55.16%)6018.7 WDrop High
35 mm²125 A97 A11.46 V (23.88%)36.5 V18.91 V (39.4%)4299.1 WDrop High
50 mm²151 A118 A8.02 V (16.72%)40.0 V13.24 V (27.58%)3009.4 WDrop High
70 mm²192 A150 A5.73 V (11.94%)42.3 V9.46 V (19.7%)2149.6 WDrop High
95 mm²232 A181 A4.22 V (8.8%)43.8 V6.97 V (14.51%)1583.9 WDrop High
120 mm²269 A210 A3.34 V (6.97%)44.7 V5.52 V (11.49%)1253.9 WDrop High
150 mm²309 A241 A2.67 V (5.57%)45.3 V4.41 V (9.19%)1003.1 WDrop High
185 mm²353 A275 A2.17 V (4.52%)45.8 V3.58 V (7.45%)813.3 WDrop High
240 mm²415 A324 A1.67 V (3.48%)46.3 V2.76 V (5.75%)627.0 W~ ≤5%
300 mm²477 A372 A1.34 V (2.79%)46.7 V2.21 V (4.6%)501.6 W✓ OK (≤3%)
400 mm²570 A445 A1.0 V (2.09%)47.0 V1.65 V (3.45%)376.2 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 375A at 25 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 375A over 25m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 375A at 48V?

At unity power factor, 375A at 48V supports 18.0 kW with a standard 400A circuit breaker.