125 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 3.31V (0.48%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.73V (0.4%)
Voltage at Load686.7 VLine Loss: 716.5 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.22 V (11.19%)612.8 V127.38 V (18.46%)16718.8 WDrop High
2.5 mm²24 A18 A46.33 V (6.71%)643.7 V76.43 V (11.08%)10031.2 WDrop High
4 mm²32 A25 A28.96 V (4.2%)661.0 V47.77 V (6.92%)6269.5 WDrop High
6 mm²41 A32 A19.31 V (2.8%)670.7 V31.84 V (4.62%)4179.7 WDrop High
10 mm²57 A44 A11.58 V (1.68%)678.4 V19.11 V (2.77%)2507.8 WDrop High
16 mm²76 A59 A7.24 V (1.05%)682.8 V11.94 V (1.73%)1567.4 WDrop High
25 mm²101 A78 A4.63 V (0.67%)685.4 V7.64 V (1.11%)1003.1 WDrop High
35 mm²125 A97 A3.31 V (0.48%)686.7 V5.46 V (0.79%)716.5 W✓ OK (≤3%)
50 mm²151 A118 A2.32 V (0.34%)687.7 V3.82 V (0.55%)501.6 W✓ OK (≤3%)
70 mm²192 A150 A1.65 V (0.24%)688.3 V2.73 V (0.4%)358.3 W✓ OK (≤3%)
95 mm²232 A181 A1.22 V (0.18%)688.8 V2.01 V (0.29%)264.0 W✓ OK (≤3%)
120 mm²269 A210 A0.97 V (0.14%)689.0 V1.59 V (0.23%)209.0 W✓ OK (≤3%)
150 mm²309 A241 A0.77 V (0.11%)689.2 V1.27 V (0.18%)167.2 W✓ OK (≤3%)
185 mm²353 A275 A0.63 V (0.09%)689.4 V1.03 V (0.15%)135.6 W✓ OK (≤3%)
240 mm²415 A324 A0.48 V (0.07%)689.5 V0.8 V (0.12%)104.5 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.06%)689.6 V0.64 V (0.09%)83.6 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.04%)689.7 V0.48 V (0.07%)62.7 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 25 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 25m at 690V (voltage drop: 3.31V or 0.48%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.