50 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 4.63V (0.67%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 4.78V (0.69%)
Voltage at Load685.4 VLine Loss: 401.2 W
Max Power & Breaker59.76 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (4.48%)659.1 V50.95 V (7.38%)2675.0 WDrop High
2.5 mm²24 A18 A18.53 V (2.69%)671.5 V30.57 V (4.43%)1605.0 WDrop High
4 mm²32 A25 A11.58 V (1.68%)678.4 V19.11 V (2.77%)1003.1 WDrop High
6 mm²41 A32 A7.72 V (1.12%)682.3 V12.74 V (1.85%)668.7 WDrop High
10 mm²57 A44 A4.63 V (0.67%)685.4 V7.64 V (1.11%)401.2 W✓ OK (≤3%)
16 mm²76 A59 A2.9 V (0.42%)687.1 V4.78 V (0.69%)250.8 W✓ OK (≤3%)
25 mm²101 A78 A1.85 V (0.27%)688.1 V3.06 V (0.44%)160.5 W✓ OK (≤3%)
35 mm²125 A97 A1.32 V (0.19%)688.7 V2.18 V (0.32%)114.6 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.13%)689.1 V1.53 V (0.22%)80.2 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.1%)689.3 V1.09 V (0.16%)57.3 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.07%)689.5 V0.8 V (0.12%)42.2 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.06%)689.6 V0.64 V (0.09%)33.4 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.04%)689.7 V0.51 V (0.07%)26.7 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.04%)689.7 V0.41 V (0.06%)21.7 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.03%)689.8 V0.32 V (0.05%)16.7 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.02%)689.8 V0.25 V (0.04%)13.4 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.02%)689.9 V0.19 V (0.03%)10.0 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 50A at 25 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 50A over 25m at 690V (voltage drop: 4.63V or 0.67%).

What is the power capacity of 50A at 690V?

At unity power factor, 50A at 690V supports 59.76 kW with a standard 50A circuit breaker.