375 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.33V (3.45%)
Voltage at Load403.4 VLine Loss: 7523.4 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2316.62 V (558.22%)0.0 V3821.34 V (920.8%)1504687.5 WDrop High
2.5 mm²24 A18 A1389.97 V (334.93%)0.0 V2292.8 V (552.48%)902812.5 WDrop High
4 mm²32 A25 A868.73 V (209.33%)0.0 V1433.0 V (345.3%)564257.8 WDrop High
6 mm²41 A32 A579.15 V (139.56%)0.0 V955.33 V (230.2%)376171.9 WDrop High
10 mm²57 A44 A347.49 V (83.73%)67.5 V573.2 V (138.12%)225703.1 WDrop High
16 mm²76 A59 A217.18 V (52.33%)197.8 V358.25 V (86.33%)141064.5 WDrop High
25 mm²101 A78 A139.0 V (33.49%)276.0 V229.28 V (55.25%)90281.2 WDrop High
35 mm²125 A97 A99.28 V (23.92%)315.7 V163.77 V (39.46%)64486.6 WDrop High
50 mm²151 A118 A69.5 V (16.75%)345.5 V114.64 V (27.62%)45140.6 WDrop High
70 mm²192 A150 A49.64 V (11.96%)365.4 V81.89 V (19.73%)32243.3 WDrop High
95 mm²232 A181 A36.58 V (8.81%)378.4 V60.34 V (14.54%)23758.2 WDrop High
120 mm²269 A210 A28.96 V (6.98%)386.0 V47.77 V (11.51%)18808.6 WDrop High
150 mm²309 A241 A23.17 V (5.58%)391.8 V38.21 V (9.21%)15046.9 WDrop High
185 mm²353 A275 A18.78 V (4.53%)396.2 V30.98 V (7.47%)12200.2 WDrop High
240 mm²415 A324 A14.48 V (3.49%)400.5 V23.88 V (5.76%)9404.3 W~ ≤5%
300 mm²477 A372 A11.58 V (2.79%)403.4 V19.11 V (4.6%)7523.4 W✓ OK (≤3%)
400 mm²570 A445 A8.69 V (2.09%)406.3 V14.33 V (3.45%)5642.6 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 375A over 250m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.