⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 10.42V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.2V (4.14%)
Voltage at Load404.6 VLine Loss: 6771.1 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2779.94 V (669.87%)0.0 V4585.6 V (1104.96%)1805625.0 WDrop High
2.5 mm²24 A18 A1667.96 V (401.92%)0.0 V2751.36 V (662.98%)1083375.0 WDrop High
4 mm²32 A25 A1042.48 V (251.2%)0.0 V1719.6 V (414.36%)677109.4 WDrop High
6 mm²41 A32 A694.99 V (167.47%)0.0 V1146.4 V (276.24%)451406.2 WDrop High
10 mm²57 A44 A416.99 V (100.48%)0.0 V687.84 V (165.74%)270843.8 WDrop High
16 mm²76 A59 A260.62 V (62.8%)154.4 V429.9 V (103.59%)169277.3 WDrop High
25 mm²101 A78 A166.8 V (40.19%)248.2 V275.14 V (66.3%)108337.5 WDrop High
35 mm²125 A97 A119.14 V (28.71%)295.9 V196.53 V (47.36%)77383.9 WDrop High
50 mm²151 A118 A83.4 V (20.1%)331.6 V137.57 V (33.15%)54168.7 WDrop High
70 mm²192 A150 A59.57 V (14.35%)355.4 V98.26 V (23.68%)38692.0 WDrop High
95 mm²232 A181 A43.89 V (10.58%)371.1 V72.4 V (17.45%)28509.9 WDrop High
120 mm²269 A210 A34.75 V (8.37%)380.3 V57.32 V (13.81%)22570.3 WDrop High
150 mm²309 A241 A27.8 V (6.7%)387.2 V45.86 V (11.05%)18056.2 WDrop High
185 mm²353 A275 A22.54 V (5.43%)392.5 V37.18 V (8.96%)14640.2 WDrop High
240 mm²415 A324 A17.37 V (4.19%)397.6 V28.66 V (6.91%)11285.2 W~ ≤5%
300 mm²477 A372 A13.9 V (3.35%)401.1 V22.93 V (5.52%)9028.1 W~ ≤5%
400 mm²570 A445 A10.42 V (2.51%)404.6 V17.2 V (4.14%)6771.1 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 375A over 300m at 415V (voltage drop: 10.42V or 2.51%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.