400 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 150 m (492.1 ft).
Copper Cable (≤3% Drop)240 mm²Drop: 9.27V (1.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.17V (1.33%)
Voltage at Load680.7 VLine Loss: 6420.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1482.64 V (214.87%) | 0.0 V | 2445.66 V (354.44%) | 1027200.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 889.58 V (128.92%) | 0.0 V | 1467.39 V (212.67%) | 616320.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 555.99 V (80.58%) | 134.0 V | 917.12 V (132.92%) | 385200.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 370.66 V (53.72%) | 319.3 V | 611.41 V (88.61%) | 256800.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 222.4 V (32.23%) | 467.6 V | 366.85 V (53.17%) | 154080.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 139.0 V (20.14%) | 551.0 V | 229.28 V (33.23%) | 96300.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 88.96 V (12.89%) | 601.0 V | 146.74 V (21.27%) | 61632.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 63.54 V (9.21%) | 626.5 V | 104.81 V (15.19%) | 44022.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 44.48 V (6.45%) | 645.5 V | 73.37 V (10.63%) | 30816.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 31.77 V (4.6%) | 658.2 V | 52.41 V (7.6%) | 22011.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 23.41 V (3.39%) | 666.6 V | 38.62 V (5.6%) | 16218.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 18.53 V (2.69%) | 671.5 V | 30.57 V (4.43%) | 12840.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 14.83 V (2.15%) | 675.2 V | 24.46 V (3.54%) | 10272.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 12.02 V (1.74%) | 678.0 V | 19.83 V (2.87%) | 8328.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 9.27 V (1.34%) | 680.7 V | 15.29 V (2.22%) | 6420.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 7.41 V (1.07%) | 682.6 V | 12.23 V (1.77%) | 5136.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 5.56 V (0.81%) | 684.4 V | 9.17 V (1.33%) | 3852.0 W | ✓ OK (≤3%) |
FAQ — 400 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 400A at 150 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 150m at 690V (voltage drop: 9.27V or 1.34%).
What is the power capacity of 400A at 690V?
At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.
Related Lengths & Currents (690V)
400A · 5m (690V)400A · 10m (690V)400A · 15m (690V)400A · 20m (690V)400A · 25m (690V)400A · 30m (690V)400A · 35m (690V)400A · 40m (690V)400A · 45m (690V)400A · 50m (690V)400A · 60m (690V)400A · 70m (690V)10A · 150m (690V)16A · 150m (690V)20A · 150m (690V)25A · 150m (690V)32A · 150m (690V)40A · 150m (690V)50A · 150m (690V)63A · 150m (690V)80A · 150m (690V)100A · 150m (690V)125A · 150m (690V)160A · 150m (690V)200A · 150m (690V)