400 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 25 m (82.0 ft).
Copper Cable (≤3% Drop)240 mm²Drop: 1.54V (0.22%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.53V (0.22%)
Voltage at Load688.5 VLine Loss: 1070.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 247.11 V (35.81%) | 442.9 V | 407.61 V (59.07%) | 171200.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 148.26 V (21.49%) | 541.7 V | 244.57 V (35.44%) | 102720.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 92.66 V (13.43%) | 597.3 V | 152.85 V (22.15%) | 64200.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 61.78 V (8.95%) | 628.2 V | 101.9 V (14.77%) | 42800.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 37.07 V (5.37%) | 652.9 V | 61.14 V (8.86%) | 25680.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 23.17 V (3.36%) | 666.8 V | 38.21 V (5.54%) | 16050.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 14.83 V (2.15%) | 675.2 V | 24.46 V (3.54%) | 10272.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 10.59 V (1.53%) | 679.4 V | 17.47 V (2.53%) | 7337.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 7.41 V (1.07%) | 682.6 V | 12.23 V (1.77%) | 5136.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 5.3 V (0.77%) | 684.7 V | 8.73 V (1.27%) | 3668.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.9 V (0.57%) | 686.1 V | 6.44 V (0.93%) | 2703.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 3.09 V (0.45%) | 686.9 V | 5.1 V (0.74%) | 2140.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.47 V (0.36%) | 687.5 V | 4.08 V (0.59%) | 1712.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 2.0 V (0.29%) | 688.0 V | 3.3 V (0.48%) | 1388.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.54 V (0.22%) | 688.5 V | 2.55 V (0.37%) | 1070.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.24 V (0.18%) | 688.8 V | 2.04 V (0.3%) | 856.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.93 V (0.13%) | 689.1 V | 1.53 V (0.22%) | 642.0 W | ✓ OK (≤3%) |
FAQ — 400 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 400A at 25 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 25m at 690V (voltage drop: 1.54V or 0.22%).
What is the power capacity of 400A at 690V?
At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.
Related Lengths & Currents (690V)
400A · 5m (690V)400A · 10m (690V)400A · 15m (690V)400A · 20m (690V)400A · 30m (690V)400A · 35m (690V)400A · 40m (690V)400A · 45m (690V)400A · 50m (690V)400A · 60m (690V)400A · 70m (690V)10A · 25m (690V)16A · 25m (690V)20A · 25m (690V)25A · 25m (690V)32A · 25m (690V)40A · 25m (690V)50A · 25m (690V)63A · 25m (690V)80A · 25m (690V)100A · 25m (690V)125A · 25m (690V)160A · 25m (690V)200A · 25m (690V)