400 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 3.09V (0.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.06V (0.44%)
Voltage at Load686.9 VLine Loss: 2140.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A494.21 V (71.62%)195.8 V815.22 V (118.15%)342400.0 WDrop High
2.5 mm²24 A18 A296.53 V (42.97%)393.5 V489.13 V (70.89%)205440.0 WDrop High
4 mm²32 A25 A185.33 V (26.86%)504.7 V305.71 V (44.31%)128400.0 WDrop High
6 mm²41 A32 A123.55 V (17.91%)566.4 V203.8 V (29.54%)85600.0 WDrop High
10 mm²57 A44 A74.13 V (10.74%)615.9 V122.28 V (17.72%)51360.0 WDrop High
16 mm²76 A59 A46.33 V (6.71%)643.7 V76.43 V (11.08%)32100.0 WDrop High
25 mm²101 A78 A29.65 V (4.3%)660.3 V48.91 V (7.09%)20544.0 WDrop High
35 mm²125 A97 A21.18 V (3.07%)668.8 V34.94 V (5.06%)14674.3 WDrop High
50 mm²151 A118 A14.83 V (2.15%)675.2 V24.46 V (3.54%)10272.0 WDrop High
70 mm²192 A150 A10.59 V (1.53%)679.4 V17.47 V (2.53%)7337.1 WDrop High
95 mm²232 A181 A7.8 V (1.13%)682.2 V12.87 V (1.87%)5406.3 WDrop High
120 mm²269 A210 A6.18 V (0.9%)683.8 V10.19 V (1.48%)4280.0 WDrop High
150 mm²309 A241 A4.94 V (0.72%)685.1 V8.15 V (1.18%)3424.0 WDrop High
185 mm²353 A275 A4.01 V (0.58%)686.0 V6.61 V (0.96%)2776.2 WDrop High
240 mm²415 A324 A3.09 V (0.45%)686.9 V5.1 V (0.74%)2140.0 W✓ OK (≤3%)
300 mm²477 A372 A2.47 V (0.36%)687.5 V4.08 V (0.59%)1712.0 W✓ OK (≤3%)
400 mm²570 A445 A1.85 V (0.27%)688.1 V3.06 V (0.44%)1284.0 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 400A at 50 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 50m at 690V (voltage drop: 3.09V or 0.45%).

What is the power capacity of 400A at 690V?

At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.