400 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 2282.7 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A913.07 V (396.99%)0.0 V1506.13 V (654.84%)365226.7 WDrop High
2.5 mm²24 A18 A547.84 V (238.19%)0.0 V903.68 V (392.9%)219136.0 WDrop High
4 mm²32 A25 A342.4 V (148.87%)0.0 V564.8 V (245.57%)136960.0 WDrop High
6 mm²41 A32 A228.27 V (99.25%)1.7 V376.53 V (163.71%)91306.7 WDrop High
10 mm²57 A44 A136.96 V (59.55%)93.0 V225.92 V (98.23%)54784.0 WDrop High
16 mm²76 A59 A85.6 V (37.22%)144.4 V141.2 V (61.39%)34240.0 WDrop High
25 mm²101 A78 A54.78 V (23.82%)175.2 V90.37 V (39.29%)21913.6 WDrop High
35 mm²125 A97 A39.13 V (17.01%)190.9 V64.55 V (28.06%)15652.6 WDrop High
50 mm²151 A118 A27.39 V (11.91%)202.6 V45.18 V (19.65%)10956.8 WDrop High
70 mm²192 A150 A19.57 V (8.51%)210.4 V32.27 V (14.03%)7826.3 WDrop High
95 mm²232 A181 A14.42 V (6.27%)215.6 V23.78 V (10.34%)5766.7 WDrop High
120 mm²269 A210 A11.41 V (4.96%)218.6 V18.83 V (8.19%)4565.3 WDrop High
150 mm²309 A241 A9.13 V (3.97%)220.9 V15.06 V (6.55%)3652.3 WDrop High
185 mm²353 A275 A7.4 V (3.22%)222.6 V12.21 V (5.31%)2961.3 WDrop High
240 mm²415 A324 A5.71 V (2.48%)224.3 V9.41 V (4.09%)2282.7 W✓ OK (≤3%)
300 mm²477 A372 A4.57 V (1.98%)225.4 V7.53 V (3.27%)1826.1 W✓ OK (≤3%)
400 mm²570 A445 A3.42 V (1.49%)226.6 V5.65 V (2.46%)1369.6 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 400A at 80 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 80m at 230V (voltage drop: 5.71V or 2.48%).

What is the power capacity of 400A at 230V?

At unity power factor, 400A at 230V supports 92.0 kW with a standard 400A circuit breaker.