425 Amp Cable Size at 10 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.61V (0.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.75V (0.33%)
Voltage at Load229.4 VLine Loss: 257.7 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A121.27 V (52.72%)108.7 V200.03 V (86.97%)51538.3 WDrop High
2.5 mm²24 A18 A72.76 V (31.63%)157.2 V120.02 V (52.18%)30923.0 WDrop High
4 mm²32 A25 A45.48 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
6 mm²41 A32 A30.32 V (13.18%)199.7 V50.01 V (21.74%)12884.6 WDrop High
10 mm²57 A44 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.8 WDrop High
16 mm²76 A59 A11.37 V (4.94%)218.6 V18.75 V (8.15%)4831.7 WDrop High
25 mm²101 A78 A7.28 V (3.16%)222.7 V12.0 V (5.22%)3092.3 WDrop High
35 mm²125 A97 A5.2 V (2.26%)224.8 V8.57 V (3.73%)2208.8 WDrop High
50 mm²151 A118 A3.64 V (1.58%)226.4 V6.0 V (2.61%)1546.2 WDrop High
70 mm²192 A150 A2.6 V (1.13%)227.4 V4.29 V (1.86%)1104.4 WDrop High
95 mm²232 A181 A1.91 V (0.83%)228.1 V3.16 V (1.37%)813.8 WDrop High
120 mm²269 A210 A1.52 V (0.66%)228.5 V2.5 V (1.09%)644.2 WDrop High
150 mm²309 A241 A1.21 V (0.53%)228.8 V2.0 V (0.87%)515.4 WDrop High
185 mm²353 A275 A0.98 V (0.43%)229.0 V1.62 V (0.71%)417.9 WDrop High
240 mm²415 A324 A0.76 V (0.33%)229.2 V1.25 V (0.54%)322.1 WDrop High
300 mm²477 A372 A0.61 V (0.26%)229.4 V1.0 V (0.43%)257.7 W✓ OK (≤3%)
400 mm²570 A445 A0.45 V (0.2%)229.5 V0.75 V (0.33%)193.3 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 10 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 425A at 10 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 10m at 230V (voltage drop: 0.61V or 0.26%).

What is the power capacity of 425A at 230V?

At unity power factor, 425A at 230V supports 97.75 kW with a standard 450A circuit breaker.