425 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.91V (0.4%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.13V (0.49%)
Voltage at Load229.1 VLine Loss: 386.5 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A181.9 V (79.09%)48.1 V300.05 V (130.46%)77307.5 WDrop High
2.5 mm²24 A18 A109.14 V (47.45%)120.9 V180.03 V (78.27%)46384.5 WDrop High
4 mm²32 A25 A68.21 V (29.66%)161.8 V112.52 V (48.92%)28990.3 WDrop High
6 mm²41 A32 A45.48 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
10 mm²57 A44 A27.29 V (11.86%)202.7 V45.01 V (19.57%)11596.1 WDrop High
16 mm²76 A59 A17.05 V (7.41%)212.9 V28.13 V (12.23%)7247.6 WDrop High
25 mm²101 A78 A10.91 V (4.75%)219.1 V18.0 V (7.83%)4638.4 WDrop High
35 mm²125 A97 A7.8 V (3.39%)222.2 V12.86 V (5.59%)3313.2 WDrop High
50 mm²151 A118 A5.46 V (2.37%)224.5 V9.0 V (3.91%)2319.2 WDrop High
70 mm²192 A150 A3.9 V (1.69%)226.1 V6.43 V (2.8%)1656.6 WDrop High
95 mm²232 A181 A2.87 V (1.25%)227.1 V4.74 V (2.06%)1220.6 WDrop High
120 mm²269 A210 A2.27 V (0.99%)227.7 V3.75 V (1.63%)966.3 WDrop High
150 mm²309 A241 A1.82 V (0.79%)228.2 V3.0 V (1.3%)773.1 WDrop High
185 mm²353 A275 A1.47 V (0.64%)228.5 V2.43 V (1.06%)626.8 WDrop High
240 mm²415 A324 A1.14 V (0.49%)228.9 V1.88 V (0.82%)483.2 WDrop High
300 mm²477 A372 A0.91 V (0.4%)229.1 V1.5 V (0.65%)386.5 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (0.3%)229.3 V1.13 V (0.49%)289.9 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 425A at 15 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 15m at 230V (voltage drop: 0.91V or 0.4%).

What is the power capacity of 425A at 230V?

At unity power factor, 425A at 230V supports 97.75 kW with a standard 450A circuit breaker.