⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.3V (0.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.38V (0.16%)
Voltage at Load229.7 VLine Loss: 128.8 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A60.63 V (26.36%)169.4 V100.02 V (43.49%)25769.2 WDrop High
2.5 mm²24 A18 A36.38 V (15.82%)193.6 V60.01 V (26.09%)15461.5 WDrop High
4 mm²32 A25 A22.74 V (9.89%)207.3 V37.51 V (16.31%)9663.4 WDrop High
6 mm²41 A32 A15.16 V (6.59%)214.8 V25.0 V (10.87%)6442.3 WDrop High
10 mm²57 A44 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 WDrop High
16 mm²76 A59 A5.68 V (2.47%)224.3 V9.38 V (4.08%)2415.9 WDrop High
25 mm²101 A78 A3.64 V (1.58%)226.4 V6.0 V (2.61%)1546.2 WDrop High
35 mm²125 A97 A2.6 V (1.13%)227.4 V4.29 V (1.86%)1104.4 WDrop High
50 mm²151 A118 A1.82 V (0.79%)228.2 V3.0 V (1.3%)773.1 WDrop High
70 mm²192 A150 A1.3 V (0.56%)228.7 V2.14 V (0.93%)552.2 WDrop High
95 mm²232 A181 A0.96 V (0.42%)229.0 V1.58 V (0.69%)406.9 WDrop High
120 mm²269 A210 A0.76 V (0.33%)229.2 V1.25 V (0.54%)322.1 WDrop High
150 mm²309 A241 A0.61 V (0.26%)229.4 V1.0 V (0.43%)257.7 WDrop High
185 mm²353 A275 A0.49 V (0.21%)229.5 V0.81 V (0.35%)208.9 WDrop High
240 mm²415 A324 A0.38 V (0.16%)229.6 V0.63 V (0.27%)161.1 WDrop High
300 mm²477 A372 A0.3 V (0.13%)229.7 V0.5 V (0.22%)128.8 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.1%)229.8 V0.38 V (0.16%)96.6 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 425A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 5m at 230V (voltage drop: 0.3V or 0.13%).

What is the power capacity of 425A at 230V?

At unity power factor, 425A at 230V supports 97.75 kW with a standard 450A circuit breaker.