425 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.53V (0.08%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.65V (0.09%)
Voltage at Load689.5 VLine Loss: 386.5 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A105.02 V (15.22%)585.0 V173.23 V (25.11%)77307.5 WDrop High
2.5 mm²24 A18 A63.01 V (9.13%)627.0 V103.94 V (15.06%)46384.5 WDrop High
4 mm²32 A25 A39.38 V (5.71%)650.6 V64.96 V (9.41%)28990.3 WDrop High
6 mm²41 A32 A26.26 V (3.81%)663.7 V43.31 V (6.28%)19326.9 WDrop High
10 mm²57 A44 A15.75 V (2.28%)674.2 V25.99 V (3.77%)11596.1 WDrop High
16 mm²76 A59 A9.85 V (1.43%)680.2 V16.24 V (2.35%)7247.6 WDrop High
25 mm²101 A78 A6.3 V (0.91%)683.7 V10.39 V (1.51%)4638.4 WDrop High
35 mm²125 A97 A4.5 V (0.65%)685.5 V7.42 V (1.08%)3313.2 WDrop High
50 mm²151 A118 A3.15 V (0.46%)686.8 V5.2 V (0.75%)2319.2 WDrop High
70 mm²192 A150 A2.25 V (0.33%)687.7 V3.71 V (0.54%)1656.6 WDrop High
95 mm²232 A181 A1.66 V (0.24%)688.3 V2.74 V (0.4%)1220.6 WDrop High
120 mm²269 A210 A1.31 V (0.19%)688.7 V2.17 V (0.31%)966.3 WDrop High
150 mm²309 A241 A1.05 V (0.15%)688.9 V1.73 V (0.25%)773.1 WDrop High
185 mm²353 A275 A0.85 V (0.12%)689.1 V1.4 V (0.2%)626.8 WDrop High
240 mm²415 A324 A0.66 V (0.1%)689.3 V1.08 V (0.16%)483.2 WDrop High
300 mm²477 A372 A0.53 V (0.08%)689.5 V0.87 V (0.13%)386.5 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.06%)689.6 V0.65 V (0.09%)289.9 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 10 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 10m at 690V (voltage drop: 0.53V or 0.08%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.