425 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 2.36V (0.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.92V (0.42%)
Voltage at Load687.6 VLine Loss: 1739.4 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A472.59 V (68.49%)217.4 V779.55 V (112.98%)347883.8 WDrop High
2.5 mm²24 A18 A283.55 V (41.09%)406.4 V467.73 V (67.79%)208730.2 WDrop High
4 mm²32 A25 A177.22 V (25.68%)512.8 V292.33 V (42.37%)130456.4 WDrop High
6 mm²41 A32 A118.15 V (17.12%)571.9 V194.89 V (28.24%)86970.9 WDrop High
10 mm²57 A44 A70.89 V (10.27%)619.1 V116.93 V (16.95%)52182.6 WDrop High
16 mm²76 A59 A44.31 V (6.42%)645.7 V73.08 V (10.59%)32614.1 WDrop High
25 mm²101 A78 A28.36 V (4.11%)661.6 V46.77 V (6.78%)20873.0 WDrop High
35 mm²125 A97 A20.25 V (2.94%)669.7 V33.41 V (4.84%)14909.3 WDrop High
50 mm²151 A118 A14.18 V (2.05%)675.8 V23.39 V (3.39%)10436.5 WDrop High
70 mm²192 A150 A10.13 V (1.47%)679.9 V16.7 V (2.42%)7454.7 WDrop High
95 mm²232 A181 A7.46 V (1.08%)682.5 V12.31 V (1.78%)5492.9 WDrop High
120 mm²269 A210 A5.91 V (0.86%)684.1 V9.74 V (1.41%)4348.5 WDrop High
150 mm²309 A241 A4.73 V (0.68%)685.3 V7.8 V (1.13%)3478.8 WDrop High
185 mm²353 A275 A3.83 V (0.56%)686.2 V6.32 V (0.92%)2820.7 WDrop High
240 mm²415 A324 A2.95 V (0.43%)687.0 V4.87 V (0.71%)2174.3 WDrop High
300 mm²477 A372 A2.36 V (0.34%)687.6 V3.9 V (0.56%)1739.4 W✓ OK (≤3%)
400 mm²570 A445 A1.77 V (0.26%)688.2 V2.92 V (0.42%)1304.6 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 45m at 690V (voltage drop: 2.36V or 0.34%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.