⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 5.25V (1.31%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.5V (1.62%)
Voltage at Load394.7 VLine Loss: 3865.4 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1050.2 V (262.55%)0.0 V1732.34 V (433.08%)773075.0 WDrop High
2.5 mm²24 A18 A630.12 V (157.53%)0.0 V1039.4 V (259.85%)463845.0 WDrop High
4 mm²32 A25 A393.83 V (98.46%)6.2 V649.63 V (162.41%)289903.1 WDrop High
6 mm²41 A32 A262.55 V (65.64%)137.4 V433.08 V (108.27%)193268.7 WDrop High
10 mm²57 A44 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
16 mm²76 A59 A98.46 V (24.61%)301.5 V162.41 V (40.6%)72475.8 WDrop High
25 mm²101 A78 A63.01 V (15.75%)337.0 V103.94 V (25.99%)46384.5 WDrop High
35 mm²125 A97 A45.01 V (11.25%)355.0 V74.24 V (18.56%)33131.8 WDrop High
50 mm²151 A118 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
70 mm²192 A150 A22.5 V (5.63%)377.5 V37.12 V (9.28%)16565.9 WDrop High
95 mm²232 A181 A16.58 V (4.15%)383.4 V27.35 V (6.84%)12206.4 WDrop High
120 mm²269 A210 A13.13 V (3.28%)386.9 V21.65 V (5.41%)9663.4 WDrop High
150 mm²309 A241 A10.5 V (2.63%)389.5 V17.32 V (4.33%)7730.7 WDrop High
185 mm²353 A275 A8.52 V (2.13%)391.5 V14.05 V (3.51%)6268.2 WDrop High
240 mm²415 A324 A6.56 V (1.64%)393.4 V10.83 V (2.71%)4831.7 WDrop High
300 mm²477 A372 A5.25 V (1.31%)394.7 V8.66 V (2.17%)3865.4 W✓ OK (≤3%)
400 mm²570 A445 A3.94 V (0.98%)396.1 V6.5 V (1.62%)2899.0 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 425A at 100 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 100m at 400V (voltage drop: 5.25V or 1.31%).

What is the power capacity of 425A at 400V?

At unity power factor, 425A at 400V supports 294.45 kW with a standard 450A circuit breaker.