425 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.68V (2.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.75V (8.15%)
Voltage at Load224.3 VLine Loss: 2415.8 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3031.67 V (1318.12%)0.0 V5000.83 V (2174.28%)1288458.3 WDrop High
2.5 mm²24 A18 A1819.0 V (790.87%)0.0 V3000.5 V (1304.57%)773075.0 WDrop High
4 mm²32 A25 A1136.88 V (494.29%)0.0 V1875.31 V (815.35%)483171.9 WDrop High
6 mm²41 A32 A757.92 V (329.53%)0.0 V1250.21 V (543.57%)322114.6 WDrop High
10 mm²57 A44 A454.75 V (197.72%)0.0 V750.12 V (326.14%)193268.7 WDrop High
16 mm²76 A59 A284.22 V (123.57%)0.0 V468.83 V (203.84%)120793.0 WDrop High
25 mm²101 A78 A181.9 V (79.09%)48.1 V300.05 V (130.46%)77307.5 WDrop High
35 mm²125 A97 A129.93 V (56.49%)100.1 V214.32 V (93.18%)55219.6 WDrop High
50 mm²151 A118 A90.95 V (39.54%)139.1 V150.03 V (65.23%)38653.8 WDrop High
70 mm²192 A150 A64.96 V (28.25%)165.0 V107.16 V (46.59%)27609.8 WDrop High
95 mm²232 A181 A47.87 V (20.81%)182.1 V78.96 V (34.33%)20344.1 WDrop High
120 mm²269 A210 A37.9 V (16.48%)192.1 V62.51 V (27.18%)16105.7 WDrop High
150 mm²309 A241 A30.32 V (13.18%)199.7 V50.01 V (21.74%)12884.6 WDrop High
185 mm²353 A275 A24.58 V (10.69%)205.4 V40.55 V (17.63%)10447.0 WDrop High
240 mm²415 A324 A18.95 V (8.24%)211.1 V31.26 V (13.59%)8052.9 WDrop High
300 mm²477 A372 A15.16 V (6.59%)214.8 V25.0 V (10.87%)6442.3 WDrop High
400 mm²570 A445 A11.37 V (4.94%)218.6 V18.75 V (8.15%)4831.7 W~ ≤5%

FAQ — 425 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 425A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 250m at 230V (voltage drop: 5.68V or 2.47%).

What is the power capacity of 425A at 230V?

At unity power factor, 425A at 230V supports 97.75 kW with a standard 450A circuit breaker.