425 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.58V (0.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.95V (0.47%)
Voltage at Load413.4 VLine Loss: 1159.6 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A315.06 V (75.92%)99.9 V519.7 V (125.23%)231922.5 WDrop High
2.5 mm²24 A18 A189.04 V (45.55%)226.0 V311.82 V (75.14%)139153.5 WDrop High
4 mm²32 A25 A118.15 V (28.47%)296.9 V194.89 V (46.96%)86970.9 WDrop High
6 mm²41 A32 A78.77 V (18.98%)336.2 V129.93 V (31.31%)57980.6 WDrop High
10 mm²57 A44 A47.26 V (11.39%)367.7 V77.96 V (18.78%)34788.4 WDrop High
16 mm²76 A59 A29.54 V (7.12%)385.5 V48.72 V (11.74%)21742.7 WDrop High
25 mm²101 A78 A18.9 V (4.56%)396.1 V31.18 V (7.51%)13915.4 WDrop High
35 mm²125 A97 A13.5 V (3.25%)401.5 V22.27 V (5.37%)9939.5 WDrop High
50 mm²151 A118 A9.45 V (2.28%)405.5 V15.59 V (3.76%)6957.7 WDrop High
70 mm²192 A150 A6.75 V (1.63%)408.2 V11.14 V (2.68%)4969.8 WDrop High
95 mm²232 A181 A4.97 V (1.2%)410.0 V8.21 V (1.98%)3661.9 WDrop High
120 mm²269 A210 A3.94 V (0.95%)411.1 V6.5 V (1.57%)2899.0 WDrop High
150 mm²309 A241 A3.15 V (0.76%)411.8 V5.2 V (1.25%)2319.2 WDrop High
185 mm²353 A275 A2.55 V (0.62%)412.4 V4.21 V (1.02%)1880.5 WDrop High
240 mm²415 A324 A1.97 V (0.47%)413.0 V3.25 V (0.78%)1449.5 WDrop High
300 mm²477 A372 A1.58 V (0.38%)413.4 V2.6 V (0.63%)1159.6 W✓ OK (≤3%)
400 mm²570 A445 A1.18 V (0.28%)413.8 V1.95 V (0.47%)869.7 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 30 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 30m at 415V (voltage drop: 1.58V or 0.38%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.