425 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.31V (0.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.62V (0.39%)
Voltage at Load413.7 VLine Loss: 966.3 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A262.55 V (63.27%)152.4 V433.08 V (104.36%)193268.7 WDrop High
2.5 mm²24 A18 A157.53 V (37.96%)257.5 V259.85 V (62.61%)115961.2 WDrop High
4 mm²32 A25 A98.46 V (23.72%)316.5 V162.41 V (39.13%)72475.8 WDrop High
6 mm²41 A32 A65.64 V (15.82%)349.4 V108.27 V (26.09%)48317.2 WDrop High
10 mm²57 A44 A39.38 V (9.49%)375.6 V64.96 V (15.65%)28990.3 WDrop High
16 mm²76 A59 A24.61 V (5.93%)390.4 V40.6 V (9.78%)18118.9 WDrop High
25 mm²101 A78 A15.75 V (3.8%)399.2 V25.99 V (6.26%)11596.1 WDrop High
35 mm²125 A97 A11.25 V (2.71%)403.7 V18.56 V (4.47%)8282.9 WDrop High
50 mm²151 A118 A7.88 V (1.9%)407.1 V12.99 V (3.13%)5798.1 WDrop High
70 mm²192 A150 A5.63 V (1.36%)409.4 V9.28 V (2.24%)4141.5 WDrop High
95 mm²232 A181 A4.15 V (1.0%)410.9 V6.84 V (1.65%)3051.6 WDrop High
120 mm²269 A210 A3.28 V (0.79%)411.7 V5.41 V (1.3%)2415.9 WDrop High
150 mm²309 A241 A2.63 V (0.63%)412.4 V4.33 V (1.04%)1932.7 WDrop High
185 mm²353 A275 A2.13 V (0.51%)412.9 V3.51 V (0.85%)1567.0 WDrop High
240 mm²415 A324 A1.64 V (0.4%)413.4 V2.71 V (0.65%)1207.9 WDrop High
300 mm²477 A372 A1.31 V (0.32%)413.7 V2.17 V (0.52%)966.3 W✓ OK (≤3%)
400 mm²570 A445 A0.98 V (0.24%)414.0 V1.62 V (0.39%)724.8 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 25m at 415V (voltage drop: 1.31V or 0.32%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.