425 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.79V (0.19%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.97V (0.23%)
Voltage at Load414.2 VLine Loss: 579.8 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A157.53 V (37.96%)257.5 V259.85 V (62.61%)115961.2 WDrop High
2.5 mm²24 A18 A94.52 V (22.78%)320.5 V155.91 V (37.57%)69576.8 WDrop High
4 mm²32 A25 A59.07 V (14.23%)355.9 V97.44 V (23.48%)43485.5 WDrop High
6 mm²41 A32 A39.38 V (9.49%)375.6 V64.96 V (15.65%)28990.3 WDrop High
10 mm²57 A44 A23.63 V (5.69%)391.4 V38.98 V (9.39%)17394.2 WDrop High
16 mm²76 A59 A14.77 V (3.56%)400.2 V24.36 V (5.87%)10871.4 WDrop High
25 mm²101 A78 A9.45 V (2.28%)405.5 V15.59 V (3.76%)6957.7 WDrop High
35 mm²125 A97 A6.75 V (1.63%)408.2 V11.14 V (2.68%)4969.8 WDrop High
50 mm²151 A118 A4.73 V (1.14%)410.3 V7.8 V (1.88%)3478.8 WDrop High
70 mm²192 A150 A3.38 V (0.81%)411.6 V5.57 V (1.34%)2484.9 WDrop High
95 mm²232 A181 A2.49 V (0.6%)412.5 V4.1 V (0.99%)1831.0 WDrop High
120 mm²269 A210 A1.97 V (0.47%)413.0 V3.25 V (0.78%)1449.5 WDrop High
150 mm²309 A241 A1.58 V (0.38%)413.4 V2.6 V (0.63%)1159.6 WDrop High
185 mm²353 A275 A1.28 V (0.31%)413.7 V2.11 V (0.51%)940.2 WDrop High
240 mm²415 A324 A0.98 V (0.24%)414.0 V1.62 V (0.39%)724.8 WDrop High
300 mm²477 A372 A0.79 V (0.19%)414.2 V1.3 V (0.31%)579.8 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.14%)414.4 V0.97 V (0.23%)434.9 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 15m at 415V (voltage drop: 0.79V or 0.19%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.