425 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.26V (0.06%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.32V (0.08%)
Voltage at Load414.7 VLine Loss: 193.3 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A52.51 V (12.65%)362.5 V86.62 V (20.87%)38653.8 WDrop High
2.5 mm²24 A18 A31.51 V (7.59%)383.5 V51.97 V (12.52%)23192.2 WDrop High
4 mm²32 A25 A19.69 V (4.74%)395.3 V32.48 V (7.83%)14495.2 WDrop High
6 mm²41 A32 A13.13 V (3.16%)401.9 V21.65 V (5.22%)9663.4 WDrop High
10 mm²57 A44 A7.88 V (1.9%)407.1 V12.99 V (3.13%)5798.1 WDrop High
16 mm²76 A59 A4.92 V (1.19%)410.1 V8.12 V (1.96%)3623.8 WDrop High
25 mm²101 A78 A3.15 V (0.76%)411.8 V5.2 V (1.25%)2319.2 WDrop High
35 mm²125 A97 A2.25 V (0.54%)412.7 V3.71 V (0.89%)1656.6 WDrop High
50 mm²151 A118 A1.58 V (0.38%)413.4 V2.6 V (0.63%)1159.6 WDrop High
70 mm²192 A150 A1.13 V (0.27%)413.9 V1.86 V (0.45%)828.3 WDrop High
95 mm²232 A181 A0.83 V (0.2%)414.2 V1.37 V (0.33%)610.3 WDrop High
120 mm²269 A210 A0.66 V (0.16%)414.3 V1.08 V (0.26%)483.2 WDrop High
150 mm²309 A241 A0.53 V (0.13%)414.5 V0.87 V (0.21%)386.5 WDrop High
185 mm²353 A275 A0.43 V (0.1%)414.6 V0.7 V (0.17%)313.4 WDrop High
240 mm²415 A324 A0.33 V (0.08%)414.7 V0.54 V (0.13%)241.6 WDrop High
300 mm²477 A372 A0.26 V (0.06%)414.7 V0.43 V (0.1%)193.3 W✓ OK (≤3%)
400 mm²570 A445 A0.2 V (0.05%)414.8 V0.32 V (0.08%)145.0 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 5m at 415V (voltage drop: 0.26V or 0.06%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.