45 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 18.24V (2.64%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 19.26V (2.79%)
Voltage at Load671.8 VLine Loss: 1421.9 W
Max Power & Breaker53.78 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A194.6 V (28.2%)495.4 V320.99 V (46.52%)15167.2 WDrop High
2.5 mm²24 A18 A116.76 V (16.92%)573.2 V192.6 V (27.91%)9100.3 WDrop High
4 mm²32 A25 A72.97 V (10.58%)617.0 V120.37 V (17.45%)5687.7 WDrop High
6 mm²41 A32 A48.65 V (7.05%)641.4 V80.25 V (11.63%)3791.8 WDrop High
10 mm²57 A44 A29.19 V (4.23%)660.8 V48.15 V (6.98%)2275.1 W~ ≤5%
16 mm²76 A59 A18.24 V (2.64%)671.8 V30.09 V (4.36%)1421.9 W✓ OK (≤3%)
25 mm²101 A78 A11.68 V (1.69%)678.3 V19.26 V (2.79%)910.0 W✓ OK (≤3%)
35 mm²125 A97 A8.34 V (1.21%)681.7 V13.76 V (1.99%)650.0 W✓ OK (≤3%)
50 mm²151 A118 A5.84 V (0.85%)684.2 V9.63 V (1.4%)455.0 W✓ OK (≤3%)
70 mm²192 A150 A4.17 V (0.6%)685.8 V6.88 V (1.0%)325.0 W✓ OK (≤3%)
95 mm²232 A181 A3.07 V (0.45%)686.9 V5.07 V (0.73%)239.5 W✓ OK (≤3%)
120 mm²269 A210 A2.43 V (0.35%)687.6 V4.01 V (0.58%)189.6 W✓ OK (≤3%)
150 mm²309 A241 A1.95 V (0.28%)688.1 V3.21 V (0.47%)151.7 W✓ OK (≤3%)
185 mm²353 A275 A1.58 V (0.23%)688.4 V2.6 V (0.38%)123.0 W✓ OK (≤3%)
240 mm²415 A324 A1.22 V (0.18%)688.8 V2.01 V (0.29%)94.8 W✓ OK (≤3%)
300 mm²477 A372 A0.97 V (0.14%)689.0 V1.6 V (0.23%)75.8 W✓ OK (≤3%)
400 mm²570 A445 A0.73 V (0.11%)689.3 V1.2 V (0.17%)56.9 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 45A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 45A over 175m at 690V (voltage drop: 18.24V or 2.64%).

What is the power capacity of 45A at 690V?

At unity power factor, 45A at 690V supports 53.78 kW with a standard 45A circuit breaker.