125 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 16.22V (2.35%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 19.11V (2.77%)
Voltage at Load673.8 VLine Loss: 3510.9 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A540.54 V (78.34%)149.5 V891.65 V (129.22%)117031.2 WDrop High
2.5 mm²24 A18 A324.33 V (47.0%)365.7 V534.99 V (77.53%)70218.7 WDrop High
4 mm²32 A25 A202.7 V (29.38%)487.3 V334.37 V (48.46%)43886.7 WDrop High
6 mm²41 A32 A135.14 V (19.58%)554.9 V222.91 V (32.31%)29257.8 WDrop High
10 mm²57 A44 A81.08 V (11.75%)608.9 V133.75 V (19.38%)17554.7 WDrop High
16 mm²76 A59 A50.68 V (7.34%)639.3 V83.59 V (12.11%)10971.7 WDrop High
25 mm²101 A78 A32.43 V (4.7%)657.6 V53.5 V (7.75%)7021.9 WDrop High
35 mm²125 A97 A23.17 V (3.36%)666.8 V38.21 V (5.54%)5015.6 W~ ≤5%
50 mm²151 A118 A16.22 V (2.35%)673.8 V26.75 V (3.88%)3510.9 W✓ OK (≤3%)
70 mm²192 A150 A11.58 V (1.68%)678.4 V19.11 V (2.77%)2507.8 W✓ OK (≤3%)
95 mm²232 A181 A8.53 V (1.24%)681.5 V14.08 V (2.04%)1847.9 W✓ OK (≤3%)
120 mm²269 A210 A6.76 V (0.98%)683.2 V11.15 V (1.62%)1462.9 W✓ OK (≤3%)
150 mm²309 A241 A5.41 V (0.78%)684.6 V8.92 V (1.29%)1170.3 W✓ OK (≤3%)
185 mm²353 A275 A4.38 V (0.64%)685.6 V7.23 V (1.05%)948.9 W✓ OK (≤3%)
240 mm²415 A324 A3.38 V (0.49%)686.6 V5.57 V (0.81%)731.4 W✓ OK (≤3%)
300 mm²477 A372 A2.7 V (0.39%)687.3 V4.46 V (0.65%)585.2 W✓ OK (≤3%)
400 mm²570 A445 A2.03 V (0.29%)688.0 V3.34 V (0.48%)438.9 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 125A over 175m at 690V (voltage drop: 16.22V or 2.35%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.