32 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 12.97V (1.88%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 13.7V (1.98%)
Voltage at Load677.0 VLine Loss: 719.0 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A138.38 V (20.05%)551.6 V228.26 V (33.08%)7669.8 WDrop High
2.5 mm²24 A18 A83.03 V (12.03%)607.0 V136.96 V (19.85%)4601.9 WDrop High
4 mm²32 A25 A51.89 V (7.52%)638.1 V85.6 V (12.41%)2876.2 WDrop High
6 mm²41 A32 A34.59 V (5.01%)655.4 V57.07 V (8.27%)1917.4 WDrop High
10 mm²57 A44 A20.76 V (3.01%)669.2 V34.24 V (4.96%)1150.5 W~ ≤5%
16 mm²76 A59 A12.97 V (1.88%)677.0 V21.4 V (3.1%)719.0 W✓ OK (≤3%)
25 mm²101 A78 A8.3 V (1.2%)681.7 V13.7 V (1.98%)460.2 W✓ OK (≤3%)
35 mm²125 A97 A5.93 V (0.86%)684.1 V9.78 V (1.42%)328.7 W✓ OK (≤3%)
50 mm²151 A118 A4.15 V (0.6%)685.8 V6.85 V (0.99%)230.1 W✓ OK (≤3%)
70 mm²192 A150 A2.97 V (0.43%)687.0 V4.89 V (0.71%)164.4 W✓ OK (≤3%)
95 mm²232 A181 A2.18 V (0.32%)687.8 V3.6 V (0.52%)121.1 W✓ OK (≤3%)
120 mm²269 A210 A1.73 V (0.25%)688.3 V2.85 V (0.41%)95.9 W✓ OK (≤3%)
150 mm²309 A241 A1.38 V (0.2%)688.6 V2.28 V (0.33%)76.7 W✓ OK (≤3%)
185 mm²353 A275 A1.12 V (0.16%)688.9 V1.85 V (0.27%)62.2 W✓ OK (≤3%)
240 mm²415 A324 A0.86 V (0.13%)689.1 V1.43 V (0.21%)47.9 W✓ OK (≤3%)
300 mm²477 A372 A0.69 V (0.1%)689.3 V1.14 V (0.17%)38.3 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (0.08%)689.5 V0.86 V (0.12%)28.8 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 32A over 175m at 690V (voltage drop: 12.97V or 1.88%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.