45 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 16.68V (2.42%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 19.26V (2.79%)
Voltage at Load673.3 VLine Loss: 1300.0 W
Max Power & Breaker53.78 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A389.19 V (56.4%)300.8 V641.98 V (93.04%)30334.5 WDrop High
2.5 mm²24 A18 A233.52 V (33.84%)456.5 V385.19 V (55.82%)18200.7 WDrop High
4 mm²32 A25 A145.95 V (21.15%)544.1 V240.74 V (34.89%)11375.4 WDrop High
6 mm²41 A32 A97.3 V (14.1%)592.7 V160.5 V (23.26%)7583.6 WDrop High
10 mm²57 A44 A58.38 V (8.46%)631.6 V96.3 V (13.96%)4550.2 WDrop High
16 mm²76 A59 A36.49 V (5.29%)653.5 V60.19 V (8.72%)2843.9 WDrop High
25 mm²101 A78 A23.35 V (3.38%)666.6 V38.52 V (5.58%)1820.1 W~ ≤5%
35 mm²125 A97 A16.68 V (2.42%)673.3 V27.51 V (3.99%)1300.0 W✓ OK (≤3%)
50 mm²151 A118 A11.68 V (1.69%)678.3 V19.26 V (2.79%)910.0 W✓ OK (≤3%)
70 mm²192 A150 A8.34 V (1.21%)681.7 V13.76 V (1.99%)650.0 W✓ OK (≤3%)
95 mm²232 A181 A6.15 V (0.89%)683.9 V10.14 V (1.47%)479.0 W✓ OK (≤3%)
120 mm²269 A210 A4.86 V (0.71%)685.1 V8.02 V (1.16%)379.2 W✓ OK (≤3%)
150 mm²309 A241 A3.89 V (0.56%)686.1 V6.42 V (0.93%)303.3 W✓ OK (≤3%)
185 mm²353 A275 A3.16 V (0.46%)686.8 V5.21 V (0.75%)246.0 W✓ OK (≤3%)
240 mm²415 A324 A2.43 V (0.35%)687.6 V4.01 V (0.58%)189.6 W✓ OK (≤3%)
300 mm²477 A372 A1.95 V (0.28%)688.1 V3.21 V (0.47%)151.7 W✓ OK (≤3%)
400 mm²570 A445 A1.46 V (0.21%)688.5 V2.41 V (0.35%)113.8 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 45A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 45A over 350m at 690V (voltage drop: 16.68V or 2.42%).

What is the power capacity of 45A at 690V?

At unity power factor, 45A at 690V supports 53.78 kW with a standard 45A circuit breaker.